Tyco 1540 User Manual
Page 52

of IEC688:1992
Error in measurement when a
Twice the error allowed at the end of the reference
measurand is within its measuring
range adjacent to the section of the measuring
range, but outside its
range where the measurand is currently operating
reference range.
or being tested.
4.3.4 Reference conditions
Reference conditions of measurands and, where applicable, components of the measurand
Values of measured quantities, and of components of measured quantities, where the intrinsic
(headline) errors for the measured quantities apply.
Voltage
50 .. 100% of nominal
Current
10 .. 100% of nominal
Frequency
Nominal ±10%
Active power (Watt)
10 .. 100% of nominal
Voltage
Nominal ±2%
Current
10 .. 100% of nominal
Active power factor
1 .. 0.8 leading or lagging
Reactive power (VAr)
10 .. 100% of nominal
Voltage
Nominal ±2%
Current
10 .. 100% of nominal
Reactive power factor
1 .. 0.8 leading or lagging
Apparent Power (VA)
10 .. 100% of nominal
Voltage
Nominal ±2%
Current
10 .. 100% of nominal
Power factor
1 .. 0.8 leading or lagging
Voltage
Nominal ±2%
Current
40 .. 100% of nominal
4.3.5 Reference conditions of influence quantities
Values that quantities which affect measurement errors to a minor degree have to be for the
intrinsic (headline) errors for measured quantities to apply.
Ambient temperature
23°C
Input frequency
50 or 60 Hz ±2%
Input waveform
Sinusoidal (distortion factor 0.005)
Auxiliary supply voltage
Nominal ±1%
Auxiliary supply frequency
Nominal ±1%
Auxiliary supply distortion factor
0.05
Magnetic field of external origin
Terrestrial flux
50
Integra 1540, 1000, 0640, 0440, 0340, 0240 Issue 1 04/03