Tyco 1540 User Manual
Page 48

LOV
121 - 240V L-L (70.1 - 139V L-N)
MIV
241 - 480V L-L (140 - 277V L-N)
HIV
481 - 600V L-L (277 - 346V L-N)
(Voltage range is defined by factory build option.)
Nominal input voltage (a.c. rms)
57.7 to 346V L-N
100 to 600V L-L
System PT/VT primary values
1V to 400 kV
Max continuous input voltage
120% of nominal (up to 720 V max.)
Max short duration input voltage
Twice nominal (1s application repeated 10 times at
10s intervals)
Nominal input voltage burden
0.2 VA approx. per phase
Nominal input current
1 or 5 A a.c. rms
System CT primary values
Standard values up to 9999 Amps
(5 A secondaries)
(1 A on application)
Max continuous input current
120% of nominal
Max short duration current input
20 times nominal (1s application repeated 5 times at
5 min intervals)
Nominal input current burden
0.6 VA approx. per phase
4.2.2 Auxiliary Power Supply
The unit can be powered from an auxiliary a.c. or d.c. supply that is separate from the metered
supply. Versions of the unit are available to suit 100-200V 45-65 Hz a.c./d.c. and 12-48V d.c
supplies.
4.2.2.1 High Voltage version
Standard supply voltage
100 to 250V a.c. nominal ±15% (85V a.c. absolute
minimum to 287V a.c. absolute maximum) or 100V to
250V d.c. nominal +25%, -15% (85V d.c. absolute
minimum to 312V d.c. absolute maximum)
a.c. supply frequency range
45 to 66 Hz or 360 to 440 Hz (Model 0440)
a.c. supply burden
3W
4.2.2.2 Low Voltage version
d.c.supply
12 to 48V d.c.. nominal +25%, -15% (10.2V d.c. absolute
minimum to 60V d.c. absolute maximum)
d.c. supply burden
3W