Daily inspection, 7daily inspection – Toshiba G9000 User Manual
Page 90
80
G9000 Installation and Operation Manual
7
DAILY INSPECTION
Please perform the daily inspection while the UPS is running. The daily inspection items are shown in
Table 7.1.
The customers can only inspect exterior or environment of cabinet. When the customers
want to perform the detailed inspection, contact the Authorized Toshiba Service
Representatives or call Toshiba International Corporation at 1-877-867-8773.
TABLE 7.1 How to perform daily inspection
No. Subject
Procedure
Criteria and/or Action needed
Term
Period
Method/Tool
1.
Environmental
ambient
Dust or Gas
Daily
Visual check and
smelling
Ventilate room atmosphere if dusty or smelling gas.
Dewdrops
Condensation
Daily
Visual check
Fix the dripping source
Dehumidify upon necessity.
Temperature
Humidity
Daily
Thermometer
hygrometer
Temperature: 32
– 104
F Humidity: 30
– 90%
No condensation.
To be controlled at 77
F or about by A/C.
2.
Cabinet
Construction
Vibration or
Audible noise
Daily
Touch and hearing
Check if fans have irregular sound.
Contact service representative in case of
abnormalities.
Overheating
When needed Touching exterior
Contact service representative in case of
abnormalities.
Air filter clog
When needed Visual check
Clean/wipe if clogged or dusty.
3.
Operation
LCD sharpness
Brightness
Left-bottom LED
Daily
Visual check
No characters faded, illegible or any other
abnormalities.
Left-bottom LED should be green.
Contact service representative when the LED shows
red with the backlight lost.
Indication terms:
Output voltage
Output current
AC input voltage
Output frequency
Battery voltage
Battery current
DC voltage
Daily
Visual check
Check indication terms/values if within the adequate
window.
Also check indication meters on surface of optional
cabinet, if installed.
4.
LEDs
4 status LEDs
Daily
Visual check
Check if LEDs turn on, off or flash according to the
operation.
2 fault LEDs
Daily
Visual check
If UPS fault LED turns on, scroll the screen to see
fault codes and record the codes.
Contact service representative to tell about fault
codes and UPS symptom.
!
NOTE