Rated Output kVA

80

100

160

225

300

500

750

Enclosure

NEMA 1

Audible Noise

70 dB @ 1 m

73 dB @ 1 m

Listings/Standards

UL; cUL; FCC Class A-Article 47

– Part 15 B;

ISO 9001; ISO14001; ANSI C62.41 (IEEE 587 Cat. B)

UL; cUL; IEC 62040-2;

ISO 9001; ISO14001; ANSI C62.41 (IEEE 587 Cat. B)

Warranty

3 Years Parts and Labor

Emergency Power Off

Included

MONITORING

Dry Contacts Included

Yes, for Input and Output Signals

RS232 Port

Included

Intelligent Monitoring
(Optional)

SNMP; MODBus RTU; MODBus TCP; BACNET; METASYS

Display

LCD Touch Panel for Local Monitoring, Operation, and Control

TABLE 1.5.b Typical UPS Efficiencies at Various Loads

UNIT

% Full Load

20%

40%

60%

80%

100%

80 kVA

92.5%

94.3%

95.0%

95.2%

95.8%

100 kVA

92.5%

94.3%

95.0%

95.2%

95.8%

160 kVA

94.7%

95.7%

96.2%

96.5%

96.5%

225 kVA

94.9%

96.2%

96.5%

96.5%

96.5%

300 kVA

94.4%

96.3%

96.9%

97.0%

97.0%

500 kVA

94.8%

96.7%

97.0%

97.0%

97.0%

750 kVA

95.5%

96.6%

97.0%

97.0%

97.0%