Table 3.

Electric heat capacity and electrical data, models PTEE and PTHE

(i)

Nominal heating

Building circuit requirement

Voltage

(ii)

Electric

heater

Size (kW)

# of

stages

Btu/h at

230/208V

Btu/h at

265V

Total

watts

(iii)

Unit

total

amps

Minimum

ampacity

(iv)

Maximum

protection

(v)

Plug

230/208

2.0/1.6

1

6,800/

5,500

-

2000/

1600

8.9/7.9

11.4

15

6 - 15 P

230/208

3.0/2.4

1

10,200/

8,200

-

3000/

2400

13.4/11.8

17

20

6 - 20 P

230/208

5.0/4.0

1

17,100/

13,700

-

5000/

4000

22.2/19.7

28

30

6 - 30 P

265

2.0

1

-

6,800

2000

7.7

9.8

15

7 - 20 P

265

3.0

1

-

10,200

3000

11.6

14.7

15

7 - 20 P

265

5.0

1

-

17,100

5000

19.3

24.4

25

7 - 30 P

(i)

All heat pumps have electric heat.

(ii)

Minimum voltage on 230/208 volt models is 187 volts; maximum is 253 volts. Minimum voltage on 265 volt models is 239 volts; max-

imum is 292 volts.

(iii)

Total watts for 7,000 and 9,000 Btu models; add 70 watts for 12,000 and 15,000 Btu models.

(iv)

Minimum branch circuit ampacity ratings conform to the National Electric Code. However, local codes should apply.

(v)

Overcurrent protection for all units without electric heaters is 15 amps. Overcurrent protection on 265 volt models must be cartridge-

style time delay fuses.

Table 4.

Power receptacle configurations

Unit
Voltage
Rating

230/
208

230/
208

230/
208

265

265

Unit plug

Plug amp

rating

15

20

30

15/20

30

NEMA

designation

6-15P

6-20P

6-30P

7-15P/7-20P 7-30P

Receptacle

Receptacle

amp rating

20

20

30

20

30

NEMA

designation

6-20R

6-20R

6-30R

7-20R

7-30R