11.4 Grounding Wire

Be sure to ground the UPS as specified.

Using the UPS without a proper ground will deteriorate the

insulation and may cause electric shock due to leakage currents.

The resistance to ground should be 10

or less.

A grounding bus is provided on the inside of the each unit. The bus is located on the front at the bottom of

the UPS units. For the 250/300kVA unit, it is located on the top left. See chapter 7 “Dimensions and

Weight” for bus location detailed.

It is recommended that 2 AWG (or 38mm

2

) or larger cable be used for the grounding wire. The wire shall

be fed through an opening at the bottom, or through a hole on a knockout plate (250/300kVA only). See

Figure 11.5 for knockout plate detail. Only one of 2 ground buses on top and at bottom shall be

connected to the ground for 250/300kVA.

The cable end must have Amp terminal of 1/2” (12mm) diameter hole to tighten with ground bus inside

the UPS, as the ground bus has 33/64” (13mm) screw hole.

The Amp terminal and ground bus shall be tightened with a 7/16” (10mm) diameter screw.

Figure 11.6 - Earth Ground Wiring.

WARNING

< 100~225kVA >

2AWG (38mm

2

)

Ground bus

12mm or 1/2”

Terminal

Feed

Through
Opening

10mm or 7/16”

Screw

To the facility

Earth ground

< 250/300kVA >

Through knockout plate

On top (Recommended)

10mm

OR

7/16”

Screw

Another way

For grounding

Note:
Only one top or bottom should
be connected to ground.