11.3 External Breakers

The G8000 UPS units are not equipped with circuit breakers. The electrical contractor should provide

the external breakers for AC input, Bypass input, DC input, and AC output. See Figure 11.1 for the

position of the breakers.

Table 11.9 shows the minimum rating for each capacity of G8000 UPS breakers. The Bypass input and

the AC output require 4-pole breakers.

Table 11.9 External Breaker Rating.

Capacity

AC input / Bypass input / AC output

Minimum Breaker Rating

DC input

Minimum Breaker Rating

100kVA

480V - 150A

500VDC – 400A

125kVA

380V - 250A

500VDC – 600A

150kVA

480V - 225A

500VDC – 600A

180kVA

380V - 350A

500VDC – 750A

225kVA

480V - 350A

500VDC – 900A

250kVA

380V - 500A

500VDC – 1100A

300kVA

480V - 450A

500VDC – 1,200A