beautypg.com

Toshiba Uninterruptible Power System G8000 Series User Manual

Page 33

background image

32

Table 11.6 Recommended Cable Size and Tightening Torque for 250kVA UPS.

Bus Number

Cable Size

Torque to tighten

the terminal bus

1

Two 250MCM or larger

2.5~4.5 kg-m (215~386 in-lbs)

2

Two 250MCM or larger

2.5~4.5 kg-m (215~386 in-lbs)

3

Two 250MCM or larger

2.5~4.5 kg-m (215~386 in-lbs)

*4

Two 350MCM or larger

2.5~4.5 kg-m (215~386 in-lbs)

*5

Two 350MCM or larger

2.5~4.5 kg-m (215~386 in-lbs)

6

Two 250MCM or larger

2.5~4.5 kg-m (215~386 in-lbs)

7

Two 250MCM or larger

2.5~4.5 kg-m (215~386 in-lbs)

8

Two 250MCM or larger

2.5~4.5 kg-m (215~386 in-lbs)

9

Two 250MCM or larger

2.5~4.5 kg-m (215~386 in-lbs)

10

Two 250MCM or larger

2.5~4.5 kg-m (215~386 in-lbs)

11

Two 250MCM or larger

2.5~4.5 kg-m (215~386 in-lbs)

12

Two 250MCM or larger

2.5~4.5 kg-m (215~386 in-lbs)

NOTE: Maximum cable size is 600MCM.

*Two battery strings or more (consult factory if using one battery string).

Table 11.7 Recommended Cable Size and Tightening Torque for 300kVA UPS.

Bus Number

Cable Size

Torque to tighten

the terminal bus

1

Two 4/0 AWG or larger

2.5~4.5 kg-m (215~386 in-lbs)

2

Two 4/0 AWG or larger

2.5~4.5 kg-m (215~386 in-lbs)

3

Two 4/0 AWG or larger

2.5~4.5 kg-m (215~386 in-lbs)

4

Three 350 MCM or larger

2.5~4.5 kg-m (215~386 in-lbs)

*5

Three 350 MCM or larger

2.5~4.5 kg-m (215~386 in-lbs)

*6

Two 4/0 AWG or larger

2.5~4.5 kg-m (215~386 in-lbs)

7

Two 4/0 AWG or larger

2.5~4.5 kg-m (215~386 in-lbs)

8

Two 4/0 AWG or larger

2.5~4.5 kg-m (215~386 in-lbs)

9

Two 4/0 AWG or larger

2.5~4.5 kg-m (215~386 in-lbs)

10

Two 4/0 AWG or larger

2.5~4.5 kg-m (215~386 in-lbs)

11

Two 4/0 AWG or larger

2.5~4.5 kg-m (215~386 in-lbs)

12

Two 4/0 AWG or larger

2.5~4.5 kg-m (215~386 in-lbs)

NOTE: Maximum cable size is 600MCM.

*Two battery strings or more (consult factory if using one battery string).