beautypg.com

Danger, Warning – Toshiba Uninterruptible Power System G8000 Series User Manual

Page 15

background image

14

The meanings of the following label symbols are as follows:

1)

The lightning flash with arrowhead within a triangle is intended to tell the user or the service
personnel that parts inside the product are a risk of electric shock to personnel.

2)

The ground symbol in a blue circle is intended to tell the user or the service personnel the
location of the equipment-grounding conductor.

A

DANGER

CONTAINS PARTS NOT SERVICEABLE

BY THE USER

Do not remove cover

No user serviceable parts inside.

Refer servicing to qualified service

personnel.

Intended for installation in a controlled

environment.

C for 125/180kVA

USE COPPER CONDUCTORS ONLY

REFER TO INSTRUCTION MANUAL REGARDING

TIGHTENING TORQUE OF TERMINAL BLOCKS.

1

2

3

4

5

6

7

8

9

10 11 12 13

U

V

W

U

V

W

N

U

V

W

N

-

+

380V 380V 380V 375V

AC INPUT BYPASS INPUT AC OUTPUT BATTERY

B

RISK OF ELECTRIC SHOCK

This UPS receive power from more than

one source-disconnection of all sources
is required to de-energize this unit before
servicing.

Dangerous electric charge may be stored

in capacitors and associated circuitry.

Wait at least five (5) minutes for power to

dissipate then check voltage before
servicing.

D

WARNING

CRITICAL FUSE SIZING

Incorrect fuse replacement size

may result in fire or
inadequate equipment
protection.

Replace only with same type

and rating of fuse

.

C for 100/150/225kVA

USE COPPER CONDUCTORS ONLY

REFER TO INSTRUCTION MANUAL REGARDING

TIGHTENING TORQUE OF TERMINAL BLOCKS.

1

2

3

4

5

6

7

8

9

10 11 12 13

U

V

W

U

V

W

N

U

V

W

N

-

+

480V 480V 480V 400V

AC INPUT BYPASS INPUT AC OUTPUT BATTERY