Omega CNiS8DV User Manual
Page 29
Example 3: Scaling with Current/Voltage Transducer (Process) Input.
The following example include details for a specific scenario in
which a 4 - 20 mA input is to be represented as a measurement
of 0 - 100 percent.
Press
d
41) Press
d at the IN.RD prompt. Display shows IN!1 Input 1
Submenu.
Press
d
42) Display shows Input 1 value with 1
st
digit flashing.
Press
b & c 43) Use b and c buttons to enter IN!1 value.
The
IN!1 value = min. input value x conversion number
from Table 3.1
Enter 4 mA as 4 (mA) x 500 = 2000
Press
d
44) Display advances to
RD!1 Reading 1 Submenu.
Press
b & c 45) Use b and c buttons to enter RD!1 value.
This value corresponds to Input 1 in terms of some meaningful
engineering units. To show 4 mA as zero percent enter
RD!1
value = 0000.
Press
d
46) Display
IN!2 Input 2 Submenu.
Press
d
47) Display shows
IN!2 Input 2 value with 1
st
digit flashing.
The
IN!2 value = max. input value x conversion number
from Table 3.1
Enter 20 mA as 20 (mA) x 500 = 10000 (entered as 9999)
Press
b & c 48) Use b and c buttons to enter IN!2 value.
Press
d
49) Display advances to
RD!2 Reading 2 Submenu.
Press
b & c 50) Use b and c buttons to enter RD!2 value.
To show 20 mA as 100 percent enter
RD!2 value = 0100
Press
d
51) Display flashes
STRD stored message momentarily and
then advances to
ALR1 only, if a change was made, otherwise
advances to
ALR1 Alarm 1 Menu.
25