Omega CNiS8DV User Manual
Page 22
ENTER INPUT TYPE MENU:
Press
a
1) Press
a, if necessary, until CNFG prompt appears.
Press
d
2) Display advances to
INPT Input Menu.
Press
d
3) Display flashes
0-0.1, 0-1.0, 0-10 or 0-20 (0 to 100 mV,
0 to 1 V, 0 to 10 V or 0 to 20 mA).
INPUT TYPE MENU:
Press
b
4) Scroll through the available selection of input ranges
0-0.1,
0-1.0, 0-10 or 0-20 to the selection of your choice.
Press
d
5) Display shows
STRD stored message momentarily and then
advances to the
RT1B Ratiometric Operation Submenu.
Input Types:
100 mV 1 V
10 V
0 – 20 mA
Display:
0-0.1
0-1.0
0-10
0-20
RATIOMETRIC OPERATION SUBMENU:
Press
d
6) Display flashes previous selection of
ENBL Enable or DSBL
Disable.
Press
b
7) Scroll through the available selection
ENBL or DSBL
(flashing).
Press
d
8) Display shows
STRD stored message momentarily and then
advances to
RESO Input/Reading Resolution Submenu.
The Ratiometric operations are typically used for Strain gauge controller.
If your controller is configured as Process (Voltage and Current), set
RTIB to DSBL disable Ratiometric operations.
If
ENBL Ratiometric operations Enabled was selected, the changes to
the excitation voltage will be compensated through Ratio measurement.
If
DSBL Ratiometric operation Disabled was selected, any changes to
the excitation voltage will effect the output of strain gauge bridge and, as
a result, a reading of the controller.
INPUT/READING RESOLUTION SUBMENU:
Press
a
9) Display flashes previous selection of
LO Low or HI High
resolution.
Press
d
10) Scroll through the available selection
LO or HI (flashing).
Press
d
11) Display shows
STRD stored message momentarily and then
advances to
BUTN Button Selection Submenu.
If
LO Low Resolution was selected the resolution of the display is 10 µV.
If
HI High Resolution was selected the resolution of the display is 1 µV.
In case of High Resolution, the maximum input signal is 10 mV.
18