INSTALLATION

Code Requirements

Installation must be in accordance with local codes, or

in the absence of local codes, with the latest editions

of the National Fuel Gas Code, ANSI Z223.1, and the

National Electrical Code, ANSI/NFPA 70. In Canada,

installations must conform with the current CSA B149

and the Canadian Electrical Code Part 1 CSA C22.2

No.1. Where required by the authority having jurisdic-

tion, the installation must conform to American Society

of Mechanical Engineers Safety Code for Controls and

Safety Devices for Automatically Fired Boilers, CSD-1.

Mounting Base

Boiler should be mounted on a level surface. Each

boiler is designed with a built-in sub-base approved for

mounting the boiler on combustible flooring. Boiler

must NOT be installed on carpet.

In addition, the boiler shall be installed such that the

gas ignition system components are protected from

water (dripping, spraying, rain, etc.) during appliance

operation and service (circulator replacement, control

replacement, etc.)

Clearance Requirements

1. Minimum clearances from combustible materials

are listed in Table B below.

2. A front clearance of at least 24" is recommended

for adequate service of burner-tray and controls.

NOTE: This boiler should be located in an area

where water leakage will not result in damage to the

area adjacent to the appliance or to the structure.

When such locations cannot be avoided, it is

recommended that a suitable drain pan, adequately

drained, be installed under the appliance. The pan

must not restrict air flow.

Model

No.

Floor

Front

Back

Right

Left

Top

Flue

Vent

0042

0066

Comb.

4 in.

6 in.

6 in.

6 in. 16 in. 6 in.

0090

0135

0180

Comb. Alcove

6 in.

6 in.

6 in. 16 in. 6 in.

Fig. 2: Mounting Base

Table B: Minimum Clearances From Combustible Materials