2. Turn the thermostat or controller up to call for heat

and check that the vent damper indicator points to

the open position, as shown in Fig. 11.

3. Turn the thermostat or controller down again and

check that the vent damper position indicator

returns to the closed position.

The vent damper must be inspected at least once

a year by a trained, experienced service techni-

cian. The name of the person who originally

installed your vent damper is shown on the instal-

lation label. Damper must be in open position

when boiler main burners are operating.

Flair Damper

NOTE: To place vent damper in the open position to

allow burner operation: Turn the power off. Turn the

damper blade to fully open position (arrow facing

same direction as vent pipe). Turn power on.

SS

R

2

SS

2

ES

R

SC

R

1

M

2

3

4

1

JUMPER

GV

24 VAC

TR

HL

L

L

1

2

120 VAC

60Hz

TH

1

Fig. 12: System Schematic

Abbreviation

Description

M

Damper Motor

R

Relay

ES

End Switch

SS1

N/C Safety Switch

SS2

N/O Safety Switch

TR

Transformer, 120/24V

HL

High Limit

GV

24V Gas Valve

TH

Thermostat, Heating, Low Voltage

J

Jumper

R

2

4

3

J

SS HL

GV

1

ES

R

2

SC

M

24 V AC

R

1

SS

2

TH

Fig. 13: Ladder Diagram

Table G: Legend for Figures 12 & 13

Note: Circuit shown with damper in closed position, no call for

heat.