beautypg.com

Combustion chamber removal, Heat exchanger re-assembly – Raypak RAYTHERM 0135B User Manual

Page 33

background image

9. Install flue collector, jacket top and inspection pan-

els. Install top holding screws. Install draft diverter

and vent piping if so equipped.

10. If gas piping was disconnected, reconnect gas pip-

ing system and check for leakage using a soap

solution.

11. Check for correct water pressure and water level

in the system. Make sure that system pump oper-

ates immediately on the call for heat. The system

is ready for operation.

12. Within two (2) days of start-up, recheck all air

vents and expansion tank levels.

Combustion Chamber Removal

To remove combustion chamber panels, you must first

remove the heat exchanger. Remove combustion

chamber panels individually.

33

Heat Exchanger Re-assembly

1. Heat exchanger water header O-rings should be

replaced with new ones.

2. Install in/out and return water headers and install

header retainer nuts and torque nuts evenly.

3. Replace "V" baffles.

4. Install thermostat sensing bulbs in header wells

and replace bulb retaining clips.

5. Install inlet and return pipes in water headers

using pipe thread sealant.

6. Install water pressure relief valve, flow switch, and

low water cut-off devices if so equipped.

7. Open water supply and return shut-off valves. Fill

boiler and water piping system with water. Check

boiler and piping system for leaks at full line pres-

sure. Run system circulating pump for a minimum

of 1/2 hour with boiler shut off.

8. Shut down entire system and vent all radiation

units and high points in system piping. Check all

strainers for debris. Expansion tank water level

should be at the 1/4 mark and the balance of the

tank filled with air (when using Air-X-Tank).

Fig. 36: Combustion Chamber Panels—Top View

This manual is related to the following products: