1. How to connect exhaust pipes

To connect the exhaust pipes, fit the male end into the female end and clamp with pipe stopper A to prevent
slipping. The exhaust pipe can be telescoped to the required length; do not cut it.

Female end

Exhaust pipe

Pipe stopper B

Male end

Pipe stopper B

Pipe stopper A

Female end

Male end

Exhaust pipe

Fit inside

Pipe stopper A

Fit inside

Connect bent pipe

Female end

Male end

TYPES COMPATIBLE WITH EXTENSION SET

INSTALLING AN EXTENSION KIT
Installing an extension kit requires construction of an air line and the exhaust line. The air line is connected
between the Air Supply Elbow at the rear of the heater and the air inlet port on the Flue pipe.
Similarly, the exhaust line is connected between the joint pipe at the rear of the heater, and the exhaust
port on the Flue pipe.

Caution: Check to see there is no debris in pipe or hose.

HOW TO INSTALL

Example:Using 2 sets of extension set and 1 bent set.

Example:Using 80 inches slide pipe set.

Vent manifold
(comes with main unit)

Air intake elbow
(comes with main unit)

Pipe stopper A

Pipe stopper B

Pipe stopper A

Bent elbow

Pipe stopper A

Hose joint

Pipe stopper B

Exhaust pipe

Hose joint

Pipe stopper A

Pipe stopper B

Air intake hose

Vent manifold

(comes with main unit)

Air intake elbow

(comes with main unit)

Pipe stopper A

Pipe clamp

Pipe stopper B

Pipe clamp

Pipe clamp

Exhaust pipe

Pipe stopper A

40 inch straight pipe

Pipe clamp

Pipe stopper A

Pipe stopper B

Hose joint

Air intake hose

Pipe clamp