UltraGlow G36D Zero Clearance Direct Vent Gas Fireplace

16

RIDID PIPE VENTING ARRANGEMENTS - VERTICAL TERMINATIONS

(Propane & Natural Gas)

The G36D is approved for a maximum 23 ft. (7.0m) vertical, with a maximum 12 ft. (3.7m) horizontal offset
using two 90

o

elbows (two 45

o

elbows equal one 90

o

elbow) with Rigid Pipe vent systems for Propane and

Natural Gas, as per diagram 1.

The G36D is approved for a maximum 37 ft. (11.3m) straight vertical, including a maximum 20" (0.5m) horizontal
offset using two 90

o

elbow (two 45

o

elbows equal one 90

o

elbow) with Rigid Pipe vent systems for Propane

and Natural Gas, as per the diagram 2.

Vent must be supported at offsets

Maintain clearances to combustibles as listed on pages 7 and 8.

Firestops are required at each fl oor level and whenever passing through a wall.

Note: Must use optional rigid pipe adaptor when using rigid pipe vent systems (Part # 510-994).
Note: UltraGlow Direct Vent System (Flex) is only approved for horizontal terminations.