beautypg.com

Raypak RAYTHERM 0133-4001 User Manual

Page 37

background image

TYPICAL BURNER TRAY ILLUSTRATED

BURNER TRAY REMOVAL

1. Shut-off power and gas supply to the boiler.

Disconnect union(s) and pilot tubing, then
loosen and remove burner hold-down screws.

2. Disconnect wires at gas valve and slide burner

tray out.

GAS VALVE REMOVAL

1. Shut-off gas supply to the boiler. Remove gas

piping to gas valve inlet.

2. Disconnect wires, pilot tubing and bleed line, if

required.

3. Turn vertical gas pipe from manifold slightly and

unscrew gas valve.

4. Reverse above procedure to re-install.

MAIN BURNER AND ORIFICE REMOVAL

1. Remove screws and burner hold-down bracket.

NOTE: If the heat exchanger is sooted badly, the
burner hold-down bracket and spacer can become
distorted from direct flame impingement and this usu-
ally necessitates replacement of these parts.

2. Lift burners from slotted spacer and slide from

orifices. Clean with a wire brush.

3. Clean orifice(s) as necessary.

PILOT REMOVAL AND CLEANING

1. Disconnect pilot tubing at pilot and sensor/igniter

wire. Remove screws holding pilot bracket to
burner tray.

2. Remove pilot and bracket, clean pilot of debris,

small bugs, etc., with wire or small brush.

3. Replace pilot, pilot tubing, sensor ignition wires

and check for leaks.

HIGH LIMIT OR TANKSTAT REMOVAL

1. Turn off electrical power.
2. Remove front inspection panel.
3. Remove wires to high limit and loosen screws

holding high limit to cabinet.

4. Remove wedge clip holding sensing bulb in

control well.

5. Remove high limit and install a new one.
6. Check control operation before leaving job.

HEAT EXCHANGER REMOVAL

1. Shut water, gas and electricity off, close valves

and relieve pressure, remove relief valve.
Remove side inspection panels.

2. Remove top holding screws.
3. Remove draft diverter, lift and remove top and

flue collector on stack type models. Remove

inspection panels.
4. Loosen bolts and disconnect flange nuts on

in/out header, loosen union(s) at gas pipe, and
slide boiler away from piping until studs clear
the heater.

37

COMBINATION FLAME SENSOR/
IGNITER AND PILOT BURNER