Pin assignments for the co alarm system outputs, Co alarm system outputs – Paradyne COMSPHERE 3600 Series User Manual

Page 46

background image

COMSPHERE –48 Vdc Central Office Power Unit

A-4

May 1998

3000-A2-GB41-40

CO Alarm System Outputs

Both major (power) and minor (fan) alarms can be sent

to the CO alarm system via the Alarm A and Alarm B
output connectors.

Figure A-1

illustrates these connectors.

The connector on the CO Power Unit’s backplane is an
AMP 5-position single row header. The mating connector
is an AMP MTE-type connector (part number 103957-4).

The CO alarm system outputs are relay contact

closures.

Table A-3

lists the pin assignments for the CO

alarm system outputs.

Table A-3

Pin Assignments for the

CO Alarm System Outputs

Pin Number

Assigned To ...

1

Major Alarm (power failure)

2

Major Alarm (power failure)

3

No Connection

4

Minor Alarm (fan failure)

5

Minor Alarm (fan failure)

A contact closure is provided between Pin Numbers 1

and 2 to indicate a power failure. A contact closure is
provided between Pin Numbers 4 and 5 to indicate a fan
failure. Note that a major alarm signal is sent to a CO
alarm system upon a failure in either the – 48V input or
low voltage output circuits, and that a minor alarm signal
is sent if the fan speed falls below 1900 rpm.

CAUTION

The relay contacts on the CO
Power Unit for the CO alarm
system have a rating of
0.1 amp maximum at 70 Vdc
maximum.