Pin assignments for the co alarm system outputs, Co alarm system outputs – Paradyne COMSPHERE 3600 Series User Manual
Page 46
COMSPHERE –48 Vdc Central Office Power Unit
A-4
May 1998
3000-A2-GB41-40
CO Alarm System Outputs
Both major (power) and minor (fan) alarms can be sent
to the CO alarm system via the Alarm A and Alarm B
output connectors.
The connector on the CO Power Unit’s backplane is an
AMP 5-position single row header. The mating connector
is an AMP MTE-type connector (part number 103957-4).
The CO alarm system outputs are relay contact
lists the pin assignments for the CO
alarm system outputs.
Table A-3
Pin Assignments for the
CO Alarm System Outputs
Pin Number
Assigned To ...
1
Major Alarm (power failure)
2
Major Alarm (power failure)
3
No Connection
4
Minor Alarm (fan failure)
5
Minor Alarm (fan failure)
A contact closure is provided between Pin Numbers 1
and 2 to indicate a power failure. A contact closure is
provided between Pin Numbers 4 and 5 to indicate a fan
failure. Note that a major alarm signal is sent to a CO
alarm system upon a failure in either the – 48V input or
low voltage output circuits, and that a minor alarm signal
is sent if the fan speed falls below 1900 rpm.
CAUTION
The relay contacts on the CO
Power Unit for the CO alarm
system have a rating of
0.1 amp maximum at 70 Vdc
maximum.