Maximum ambient temperatures permitted, Independent mode of operation – Paradyne COMSPHERE 3600 Series User Manual

Page 18

background image

COMSPHERE –48 Vdc Central Office Power Unit

2-2

May 1998

3000-A2-GB41-40

directly above the bottom carrier should have its power
module installed in the right side of its CO power tray.
Then, the next carrier directly above should have its
power module installed in the left side of its CO power
tray, and so on for the remainder of the carriers in the
cabinet. For information on removing and installing a
power module, see the

Power Module Replacement

Instructions

section in Chapter 3.

With the power modules placed in alternating

sequence, the maximum operating ambient temperatures
listed in

Table 2-1

are permitted.

Independent Mode of Operation

In the Independent mode of operation, the left power

module (as viewed from the front of the carrier) powers
Slots 1 through 8 of the carrier and the right power
module powers Slots 9 through 16 of the carrier. The
Shared Diagnostic Unit (SDU), contained in Slot 0, is
powered by both power modules. If a power module fails,
only the service to that side of the carrier is disrupted. The
other side of the carrier is unaffected. Do not remove a

failed power module until a replacement is available. To
replace a power module, see the

Power Module

Replacement Instructions

section in Chapter 3 of this

guide.

When the power modules are configured for

Independent mode of operation, up to six carriers can be
mounted in a cabinet. The maximum ambient temperature
is 50

°

C.

The – 48 Vdc input can be provided in one of two

powering options:

Using two separate – 48 Vdc power sources and two
input power cables.

Using one – 48 Vdc power source and two input
power cables.

For maximum reliability, use the first option. For more

information on these powering options, see the

Providing

Power to a CO Power Unit

section.

To change the mode of operation, see the

Setting the

Option Straps

section.

Table 2-1

Maximum Ambient Temperatures Permitted

Maximum

Allowable Number of Stacked COMSPHERE 3000 Series

Carriers in a Cabinet

Maximum

Ambient

Temperature

3551 and 3611 DSUs

without DBMs, 3511

DSUs, 3151 and CSUs

2

3551, 3611, and 3616

DSUs with DBMs and

3811 Modems

2

3161 DSU/CSUs

1

122

°

F (50

°

C)

4

2

See Note 4

113

°

F (45

°

C)

5

3

1

3

, 2

104

°

F (40

°

C)

6

4

3

ă

95

°

F (35

°

C)

6

5

4

86

°

F (30

°

C)

6

5

5

77

°

F (25

°

C)

6

6

6

NOTES:

1

These operating ambient temperatures can be increased by 5

°

C by placing 3161 DSU/CSUs in cooler

slots (2, 3, 4, 5, 10, 11, 12, 13), or by leaving a slot empty next to each 3161 DSU/CSU.

2

Use the strictest cooling requirements when there is a mixture of units installed.

3

Requires a power module on each side, otherwise the ambient temperature must be restricted to 35

°

C.

4

A single carrier, equipped with two power modules, can operate at 50

°

C provided the cooler slots (2, 3, 4,

5, 10, 11, 12, 13) are used.