Settings for independent mode – Paradyne COMSPHERE 3600 Series User Manual

Page 23

background image

Installation

2-7

3000-A2-GB41-40

May 1998

Independent Mode

If you want to operate in Independent mode and you

plan to use either one or two – 48 Vdc power sources,
configure the option straps as shown in

Table 2-3

.

Table 2-3

Settings for Independent Mode

S1 Raised

S2 Raised

S3 Raised

S4 Raised

S5 Raised

To set the option straps for Independent mode of

operation:

"

Procedure

1. Loosen the screws on all five straps (S1 through

S5) on the CO Power Unit’s backplane so that the
screws are not touching the contacts. (Two
complete turns will suffice.)

Redundant Mode — One Source, One Cable

If you want to operate in Redundant mode and you

plan to use a single – 48 Vdc power source and a single
input power cable, configure the option straps as shown in

Table 2-4

.

Table 2-4

Settings for Redundant Mode

Using a Single – 48 Vdc Power Source

and a Single Input Power Cable

S1 Lowered

S2 Lowered

S3 Lowered

S4 Lowered

S5 Lowered

To set the option straps for Redundant mode of

operation using a single – 48 Vdc power source and a
single input power cable:

"

Procedure

1. Tighten the screws on all five straps (S1 through

S5) on the CO Power Unit’s backplane. Make sure

that the screws are securely touching the contacts,
but do not screw the straps too tight because doing
so can damage the equipment.

Redundant Mode — Two Cables

If you want to operate in Redundant mode and you

plan to use either a single – 48 Vdc power source and two
input power cables or two separate – 48 Vdc power
sources and two input power cables, configure the option
straps as shown in

Table 2-5

.

Table 2-5

Settings for Redundant Mode with Either

a Single Power Source and Two Input

Power Cables, or Two Separate

Power Sources and Two Input Power Cables

S1 Lowered

S2 Lowered

S3 Lowered

S4 Raised

S5 Raised

To set the option straps for Redundant mode of

operation with either a single power source and two input
power cables, or two separate power sources and two
input power cables:

"

Procedure

1. Tighten the screws on the S1, S2, and S3 straps on

the CO Power Unit’s backplane. Do not screw the
straps too tight because doing so can damage the
equipment. Make sure that the screws are securely
touching the contacts. Then loosen the screws on
the S4 and S5 straps. (Two complete turns will
suffice.)

NOTE

In

either Independent or

Redundant mode of operation,
the S4 and S5 straps on the
backplane must be raised
(loosened) when two separate
– 48 Vdc power sources are
used to prevent operational
problems and voltage
incompatibilities.