Installation

2-17

3000-A2-GB41-40

May 1998

Connecting the Alarm Contacts to a
6800 Series NMS Via a Modular 3611 DSU

The CO Power Unit can also send alarms to a

6800 Series NMS using the external alarm functions of a
Modular 3611 DSU. After the CO Power Unit is installed,
connect the power unit to the external leads of a Modular
3611 DSU by using an NMS adapter cable.

Before you can forward CO alarms to the 6800 Series

NMS via the external leads, you must configure the
Modular 3611 DSU for alarm forwarding by setting the
appropriate jumpers. To do this, remove the Modular 3611
DSU from the carrier and set Jumpers J20 and J21 (for
Model 3611-B3) or Jumper E5 and Switch S1-2 (for
Model 3611-B4) as shown in Table 2-6.

Table 2-6

Jumper Settings

Model

Jumper or

Switch

Setting to Enable

–48 Vdc Alarm

Monitoring

3611-B3

Jumper J20

Left

3611-B3

Jumper J21

Left

3611-B4

Jumper E5

Left

3611-B4

Switch S1-2

On

After setting the jumpers, reinstall the Modular 3611

DSU in the carrier. Then, set the firmware configuration
External Leads (Ext Leads, in the General branch)
parameter as shown:

Ext Leads: RPowr

NOTE

Remember, for

Basic or

Independent mode of
operation
, the Modular 3611
DSU (configured for alarm
forwarding) must be installed in a
different carrier (that is, a carrier
in the cabinet other than the one
you want to manage). This
arrangement ensures that all
alarm signals are forwarded even
if power has disrupted service to
the carrier.

For

Redundant mode of

operation, you may want to
install the Modular 3611 DSU in
a different carrier in the unlikely
event of a double power module
failure.