[Intake Air Temp. - Remote Controller Setting Temp.] >
[Thermostat-OFF Temp. +0.5 °C]
Operated in corresponding frequency.
•
•
•
•
Frequency is decided after a completion of the starting
control (in 60 seconds).
•
•
•
•
When Room Temp. is below [Thermostat-OFF Temp.]
continuously for 3 minutes or more, it turns to Thermostat-
OFF operation.
•
•
•
•
When room temperature almost comes to Thermostat-OFF
Temp., the operation turns to the Minimum power & fan
speed: SSLo.
•
•
•
•
[Intake Air Temp. - Remote Controller Setting Temp.] >
[Thermostat-OFF Temp. +0.5 °C]
Operated in corresponding frequency.
•
•
•
•
Frequency is decided after a completion of starting control
(in 60 seconds).
•
•
•
•
When Room Temp. is below Thermostat-OFF Temp.
continuously for 3 minutes or more, it turns to Thermostat-
OFF operation.
•
•
•
•
When room temperature almost comes to Thermostat-OFF
Temp., the operation turns to the Maximum power.
Dry
Power
TE9DKE
TE12DKE
Intake Air Temp.
Difference (°C)
Maximum
2.7kW
4.0kW
Rated
2.5kW
3.6kW
Intermediate
~
~
Minimum
0.8kW
0.8kW
(-2.50)
OFF
—
—
Heating
Power
TE9DKE
TE12DKE
Intake Air Temp.
Difference (°C)
OFF
—
—
Minimum
0.8kW
0.8kW
Intermediate
~
~
Rated
3.5kW
4.5kW
(+1.00)
Maximum
4.6kW
6.2kW
9.3.2. Dry Operation
9.3.2.1. Thermostat Control
9.3.3. Heating Operation
9.3.3.1. Thermostat Control
22
CS-TE9DKE CU-TE9DKE / CS-TE12DKE CU-TE12DKE