Piping
77
Table 47
Line charges - refrigerant per 100 ft (30m) of Type “L” copper tube
O.D.
Liquid Line, lb (kg)
1/2" 7.3
(3.3)
5/8" 11.7
(5.3)
7/8" 24.4
(11.1)
1-1/8"
41.6 (18.9)
Table 48
Outdoor condenser approximate refrigerant charge lb (kg) per circuit
Model
Fan
Speed
Lee-Temp
(includes receiver)
165
5 (2.3)
27 (12.3)
205
7 (3.2)
38 (17.2)
251
10 (4.6)
38 (17.20
308
11 (5.0)
58 (26.3)
415
15 (6.8)
75 (34.0)
510
30 (13.6)
149 (67.6)
143
17 (8)
64 (29)
214
23 (10
81 (37)
286
29 (13)
98 (44)
409
36 (16)
129 (59)
477
24 (11)
80 (36)
572
57 (26)
196 (89)