Scroll or digital scroll compressor models, Table 12 – Liebert Precision Cooling System DS User Manual
Page 30
![background image](/manuals/169140/30/background.png)
Liebert DS Dimensions and Weights
20
Figure 15 Cabinet and floor planning dimensions—upflow, air-cooled 28-42kW (8-12 ton), scroll or digital
scroll compressor models
Table 12
Weight for upflow, air-cooled, 28-42kW (8-12 ton), scroll or digital scroll compressor models
Model No.
Dry Weight, lb (kg)
approximate
028-042
Air-Cooled
1520 (689)
Dual-Cool
1670 (758)
Alternate Refrigerant
Piping Entrance
3/4"
(19mm)
Bezels
24"
(610mm)
34"
(864mm)
72"
(1829mm)
FRONT VIEW
DPN001163
Rev. 1
Shaded area indicates a
recommended minimum
clearance for component
access.
2"
(51mm)
76"
(1930mm)
1-1/2"
(38mm)
TOP VIEW
73"
(1854mm)
High Volt Connection(s)
35"
(889mm)
33"
(838mm)
Minimum required
for blower replacement
Low Volt Connection(s)
Note: Front air return unit shown. For rear
return unit, in addition to front service area
shown, also include 25" (635mm) on one side
of unit for access to rear return filter box.
See DPN001196, Figure 28.