beautypg.com

77kw (15-22 ton), all compressor models, Table 8 – Liebert Precision Cooling System DS User Manual

Page 26

background image

Liebert DS Dimensions and Weights

16

Figure 11 Cabinet and floor planning dimensions—downflow, water/glycol/GLYCOOL, 53-77kW

(15-22 ton), all compressor models

Table 8

Weights for downflow, water/glycol/GLYCOOL, 53-77kW (15-22 ton), all compressor models

Compressor

Type

Model

Dry Weight, lb (kg), Approximate

053

070

077

Semi-Hermetic

Compressor

Water/Glycol

2650 (1205)

2700 (1228)

2750 (1250)

GLYCOOL/Dual-Cool

2830 (1287)

2880 (1310)

2930 (1332)

Scroll or

Digital Scroll

Compressor

Water/Glycol

2220 (1010)

2270 (1032)

2320 (1055)

GLYCOOL/Dual-Cool

2400 (1091)

2450 (1114)

2500 (1137)

Notes: Filters are accessible
through top of unit only.
Downflow electrical
connections can be made
from top or bottom of unit.

Shaded area indicates a
recommended minimum
clearance for component
access.

Required for

condenser cleanout

15"

(381mm)

34"

(864mm)

DPN000931
Rev. 3

76"

(1930mm)

TOP VIEW

Air Inlet Opening

Secondary Entrance
High Volt Connection(s)

Secondary Entrance
Low Volt Connections

80" (2032mm)

Opening

35"

(889mm

24-5/8" (625mm)

Opening

3/4" (20mm)

Bezels

Secondary Condenser
Fluid Piping Entrance

Condenser Cleanout Access

33"

(838mm)

24"

(610mm)

FRONT VIEW

2"

(51mm)

108"

(2743mm)

109"

(2769mm)

Minimum required
for filter replacement