beautypg.com

Start-up – Lochinvar 800 User Manual

Page 50

background image

Installation & Operation Manual

50

10

Start-up

Check/control water chemistry

Do not use petroleum-based cleaning or
sealing compounds in the boiler system.
Damage to elastomer seals and gaskets in
the system could occur, resulting in
substantial property damage.

Hardness less than 7 grains

1.

Consult local water treatment companies for hard water
areas (above 7 grains hardness).

Chlorine concentration less than 200 ppm

1.

Do not fill boiler or operate with water containing
chlorine in excess of 200 ppm.

2.

Filling with chlorinated fresh water should be acceptable
since drinking water chlorine levels are much lower.

3.

Do not use the boiler to directly heat swimming pool or
spa water.

Test/replace freeze protection fluid

1.

For systems using freeze protection fluids, follow fluid
manufacturer’s instructions.

2.

Freeze protection fluid must be replaced periodically due
to degradation of inhibitors over time. Follow all fluid
manufacturer’s instructions.

Freeze protection (when used)

1.

Determine freeze protection fluid quantity using system
water content, following fluid manufacturer’s
instructions. Boiler water content is listed on page 7.
Remember to include expansion tank water content.

2.

Local codes may require a backflow preventer or actual
disconnect from city water supply.

3.

When using freeze protection fluid with automatic fill,
install a water meter to monitor water makeup. Freeze
protection fluid may leak before the water begins to leak,
causing concentration to drop, reducing the freeze
protection level.

Fill and test water system

1.

Fill system only after ensuring the water meets the
requirements of this manual.

2.

Close manual and automatic air vents and boiler drain
valve.

3.

Fill to correct system pressure. Correct pressure will vary
with each application.

a.

The minimum cold water fill pressure for a
commercial system is 12 psi (82.7 kPa).

b.

Pressure will rise when boiler is turned on and
system water temperature increases.

Eliminate all system leaks. Continual fresh
makeup water will reduce boiler life.
Minerals can build up in the heat
exchanger, reducing heat transfer,
overheating the heat exchanger, and
causing heat exchanger failure.

Purge air from water system

1.

Purge air from system:
a.

Connect a hose to the purge valve (see purge/drain
valves, in piping diagrams on page 41). Route the
hose to an area where water can drain and be seen.

b.

Close the boiler or system isolation valve between
the purge valve and fill connection to the system.

c.

Close zone isolation valves.

d.

Open quick-fill valve on cold water makeup line.

e.

Open purge valve.

f.

One zone at a time, open the isolation valves. Allow
water to run through the zone, pushing out the air.
Run until no noticeable air flow is present. Close the
zone isolation valves and proceed with the next zone.
Follow this procedure until all zones are purged.

g.

Close the quick-fill water valve and purge valve and
remove the hose. Open all isolation valves. Watch
that system pressure rises to correct cold-fill
pressure.

h.

After the system has operated for a while, eliminate
any residual air by using the manual air vents located
throughout the system.

i.

If purge valves are not installed in the system, open
the manual air vents in the system one at a time,
beginning with the lowest floor. Close the vent when
water squirts out. Repeat with remaining vents.

2.

Open automatic air vent (diaphragm-type or bladder-
type expansion tank systems only) one turn.

3.

Open other vents:
a.

Starting on the lowest floor, open air vents one at a
time until water squirts out.

b.

Repeat with remaining vents.

4.

Refill to correct pressure.

4.

At initial fill and during boiler startup and testing, check
system thoroughly for any leaks. Repair all leaks before
proceeding further.

ƽ WARNING

ƽ CAUTION