Sidewall direct venting

(continued)

Sidewall termination – optional concentric vent: Models 399 - 600 Only

Multiventing sidewall terminations

When two (2) or more direct vent appliances are vented near
each other, each appliance must be individually vented (see
FIG. 4-12). NEVER common vent or breach vent this appliance.
When two (2) or more direct vent appliances are vented near
each other, two (2) vent terminations may be installed as shown
in FIG. 4-12. The next two (2) terminations must be at least 36
inches (914 mm) away from the first two (2) terminations. It is
important that vent terminations be made as shown to avoid
recirculation of flue gases. Dimension A in FIG. 4-12 represents
the distance between pipes or rain shields, as touching or a
2 inch (51 mm) maximum separation.

VENT

COMBUSTION
AIR

36"

(914 MM)

"A"

Figure 4-12 Concentric Vent and Combustion Air Termination Dimension A as
Touching or 2 inches (51 mm) Maximum Separation

COMBUSTION AIR

VENT

VENT

COMBUSTION AIR

STRAP

(FIELD SUPPLIED)

ELBOW

(FIELD SUPPLIED)

Figure 4-11 Concentric Vent Sidewall Attachment

DO NOT use field-supplied couplings to
extend pipes. Airflow restriction will
occur and may cause intermittent
operation.

9.

Cement appliance combustion air and vent pipes to the
concentric vent termination assembly. See FIG. 4-11
for proper pipe attachment.

10. Operate the appliance one (1) heat cycle to ensure

combustion air and vent pipes are properly connected
to the concentric vent termination connections.