Sidewall direct venting, Vent/air termination – sidewall, Installation & operation manual – Lochinvar 800 User Manual
Page 25: Prepare wall penetrations

Installation & Operation Manual
25
12” (305 MM)
MIN
BIRD
SCREEN
(TYPICAL)
12” (305 MM)
MIN
12” (305 MM)
MIN
Figure 4-3B Alternate Clearance to Gravity Air
Inlets w/Field Supplied Fittings
36” (914 MM)
MIN
7’ (2.1 M) MIN ABOVE ANY
PUBLIC WALKWAY
IF LESS
THAN 10’ (3 M)
FORCED AIR
INLET
BIRD
SCREEN
(TYPICAL)
Figure 4-4B Alternate Clearance to Forced Air Inlets
w/Field Supplied Fittings 
4
Sidewall direct venting
(continued)
Vent/air termination – sidewall
FORCED AIR
INLET
VENT / AIR
TERMINATION
7' MIN. ABOVE ANY
PUBLIC WALKWAY
IF LESS
THAN 10’
36"
MIN.
Figure 4-4A Clearance to Forced Air Inlets
VENT PIPING
GALVANIZED
THIMBLE
VENT CAP
AIR PIPING
WALL PLATE
VENT PLATE
Figure 4-5A Sidewall Termination Assembly
Prepare wall penetrations
1.
Use the factory supplied wall plate as a template to locate 
the vent and air intake holes and mounting holes. 
Air pipe penetration:
a.
Cut a hole for the air pipe. Size the air pipe hole as 
close as desired to the air pipe outside diameter.
Vent pipe penetration:
a.
Cut a hole for the vent pipe. For either combustible or 
noncombustible construction, size the vent pipe hole 
with at least a 1/2 inch clearance around the vent pipe 
outer diameter:
• 5½ inch hole (140 mm) hole for 4 inch (102 mm)
vent pipe
• 7½ inch hole (191 mm) hole for 6 inch (152 mm)
vent pipe
Drill 3/16" diameter holes for inserting the plastic anchors 
into the wall. 
2.
Install the vent and air intake piping through the wall into 
the vent plate openings. Seal all gaps between the pipes and 
wall. Use RTV silicone sealant to seal the air pipe. Use the 
cement/primer listed in Table 3A on page 18 to seal the vent 
pipe.
3.
Mount and secure the vent plate to the wall using stainless 
steel screws. Seal around the plate to the wall assuring no 
air gaps.
4.
Assemble the vent cap to the vent plate (see FIG. 4-4A). 
Insert the stainless steel screws into the vent cap screw hole 
openings and securely attach the vent cap to the vent plate.
5.
Seal all wall cavities.