Installation & Operation Manual

18

3

General venting

6.

Priming and Cementing:
a.

Handle fittings and pipes carefully to prevent
contamination of surfaces.

b.

Apply a liberal even coat of primer to the fitting
socket.

c.

Apply a liberal even coat of primer to the pipe end to
approximately 1/2" beyond the socket depth.

d.

Apply a second primer coat to the fitting socket.

e.

While primer is still wet, apply an even coat of
approved cement to the pipe equal to the depth of
the fitting socket.

f.

While primer is still wet, apply an even coat of
approved cement to the fitting socket.

g.

Apply a second coat of cement to the pipe.

h.

While the cement is still wet, insert the pipe into the
fitting, if possible twist the pipe a 1/4 turn as you insert
it. NOTE: If voids are present, sufficient cement was
not applied and joint could be defective.

j.

Wipe excess cement from the joint removing ring or
beads as it will needlessly soften the pipe.

Table 3A Vent Pipe, and Fittings

PVC/CPVC air intake/vent connections

1.

Combustion Air Intake Connector (FIG.’s 3-9 and 3-10) - Used to provide combustion air directly to the unit from
outdoors. A fitting is provided on the unit for final connection. Combustion air piping must be supported per guidelines
listed in the National Mechanical Code, Section 305, Table 305.4 or as local codes dictate.

2.

Vent Connector (FIG.’s 3-9 and 3-10) - Used to provide a passageway for conveying combustion gases to the outside.
Transition fittings are provided with the unit for final connection. Vent piping must be supported per the National Building
Code, Section 305, Table 305.4 or as local codes dictate.

6” COUPLING

(FIELD SUPPLIED)

6” CPVC

STARTER

PIECE

(FACTORY SUPPLIED)

VENT

AIR

THE 6” STAINLESS STEEL ADAPTER SUPPLIED
WITH THE BOILER MUST BE USED FOR VENT
CONNECTION TO PVC/CPVC. THE 6” CPVC
STARTER PIECE MUST BE USED FOR PVC ONLY.

Figure 3-10 Near Boiler PVC/CPVC Venting -
Models 700 - 800

VENT

AIR

4" CPVC PIPE SUPPLIED WITH
BOILER MUST BE USED FOR VENT CONNECTION

NOTE:

CPVC VENT PIPE AND VENT FITTINGS MUST BE USED IN

CLOSET AND ALCOVE INSTALLATIONS.

*

* 4” CPVC STREET ELBOW
MAY BE SUBSTITUTED

Figure 3-9 Near Boiler PVC/CPVC Venting - Models 399 - 600

All vent pipe materials and fittings must comply with the following:

Item

Material

Standards for installation in:

United States

Canada

Vent pipe and fittings

PVC schedule 40

ANSI/ASTM D1785

CPVC and PVC venting must be ULC-

S636 Certified. IPEX is an approved

manufacturer in Canada supplying vent

material listed to ULC-S636.

PVC-DWV

ANSI/ASTM D2665

CPVC schedule 40

ANSI/ASTM F441

AL29-4C

UL1738

ULC-S636

Pipe cement/primer

PVC

ANSI/ASTM D2564

IPEX System 636

Cements & Primers

CPVC

ANSI/ASTM F493

NOTICE: DO NOT USE CELLULAR (FOAM) CORE PIPE

Approved Stainless Steel Vent Manufacturers

Make

Model

ProTech Systems (Simpson Dura-Vent Co.)

FasNSeal Vent

Z-Flex (Nova Flex Group)

Z-Vent

Heat Fab (Selkirk Corporation)

Saf-T Vent