Vertical direct venting, Vent/air termination – vertical, Installation & operation manual – Lochinvar 800 User Manual

Page 30: Determine location

background image

Installation & Operation Manual

30

5

Vertical direct venting

Vent/air termination – vertical

Follow instructions below when
determining vent location to avoid
possibility of severe personal injury, death
or substantial property damage.

Installation must comply with local
requirements and with the National Fuel
Gas Code, ANSI Z223.1 for U.S.
installations or CSA B149.1 for Canadian
installations.

Determine location

Locate the vent/air terminations using the following
guidelines:

1. The total length of piping for vent or air must not exceed

the limits given in the General Venting Section on page 21
of this manual.

2.

The vent must terminate at least 3 feet above the highest
place in which the vent penetrates the roof and at least
2 feet above any part of a building within 10 horizontal
feet.

3.

The air piping must terminate in a down-turned 180°
return pipe no further than 2 feet (.6 m) from the center
of the vent pipe. This placement avoids recirculation of
flue products into the combustion air stream.

4.

The vent piping must terminate in an up-turned coupling
as shown in FIG. 5-1A. The top of the coupling must be
at least 1 foot above the air intake. When the vent
termination uses a rain cap as illustrated in FIG. 5-1B
maintain at least 36" (914 mm) above the air inlet. The
air inlet pipe and vent pipe can be located in any desired
position on the roof, but must always be no further than
2 feet (.6 m) apart and with the vent termination at least
1 foot above the air intake.

ALTERNATE INTAKE LOCATIONS:
INTAKE PIPES MAY BE LOCATED
ANYWHERE WITHIN 24" (610 MM)
OF VENT PIPE

BIRD SCREEN
(TYPICAL)

COUPLING
(FIELD SUPPLIED)

VENT OUTLET
12" MINIMUM
ABOVE AIR INLET

6" (152 MM) MINIMUM
ABOVE ROOF /
SNOW LINE

VENT

COMBUSTION
AIR

Figure 5-1A PVC/CPVC Vertical Termination of Air and
Vent

5.

Locate terminations so they are not likely to be damaged by
foreign objects, such as stones or balls, or subject to buildup
of leaves or sediment.

ƽ WARNING

NOTICE

ƽ WARNING

Do not connect any other appliance to the
vent pipe or multiple boilers to a common
vent pipe. Failure to comply could result in
severe personal injury, death, or substantial
property damage.

ƽ WARNING Rooftop vent and air inlet terminations

must terminate in the same pressure zone,
unless vertical vent sidewall air is set up as
shown in the General Venting - Vertical
Vent, Sidewall Air Section.

6" (152 MM) MINIMUM

ABOVE ROOF /

SNOW LINE

VENT

COM,BUSTION

AIR

ALTERNATE INTAKE LOCATIONS:
INTAKE PIPES MAY BE LOCATED
ANYWHERE WITHIN 24” (610 MM)
OF VENT PIPE

VENT OUTLET

36” (914 MM) MINIMUM

ABOVE AIR INLET

BIRD SCREEN

(TYPICAL)

Figure 5-1B Stainless Steel Vertical Termination of Air
and Vent