Appendix b, Installation and service manual, Adjust menu settings for operating modes – Lochinvar GAS HEATER FOR COMMERICAL POOL APPLICATIONS User Manual

Page 59: View menu information, Advanced settings

background image

Advanced settings:

By pressing the Select key in the View mode while viewing the
Boiler

ΔT reading (or the Supply Sensor temperature if the

Pool Supply sensor is connected), the Boiler On hours will be
displayed, indicated by the text BOIL ON in the display. This
is the total number of hours the pool heater has been heating
the pool.
By pressing the Select key in the Adjust mode while viewing
the Pool DIFF setting, the Boiler Inlet Minimum setting will be
displayed, indicated by the text BOIL IN MIN in the display.
The control will adjust the position of the 3-way automatic
bypass valve in order to maintain the inlet temperature at this
setting. The default is 130°F.
By pressing the Select key again, the Boiler Maximum setting
will be displayed, indicated by the text BOIL MAX in the
display. The control will shut off the heater whenever the
outlet temperature from the heater exceeds this setting. The
default value is 200°F.
If a Pool Supply sensor is connected, then by pressing the
Select key again, the Supply Target setting will be displayed,
indicated by the text SUP TARGET in the display. The

control will shut off the heater whenever the pool supply
temperature exceeds this setting. The default value is 100°F.
If a Pool Supply sensor is connected, then by pressing the
Select key again, the Supply Differential setting will be
displayed, indicated by the text SUP DIFF in the display.
After the control has turned off the heater because the pool
supply temperature exceeded the Pool Supply setting, the pool
supply temperature must drop by this amount before the
control will allow the heater to start up again. The default
value is 20°F.
By pressing the Select key again, the Valve Speed setting will
be displayed, indicated by the arrow pointing to the text
SPEED on the overlay. This setting is used to control the
responsiveness of the 3-way automatic bypass valve, and
should only be adjusted under the direction of Lochinvar’s
Technical Services personnel. The default setting is 20
seconds.
By pressing the Select key again, the pump Delay setting is
displayed, indicated by the DLY on the display. This is the
time that the heater pump will continue to run after the control
turns the heater off. The default value is 20 minutes.

59

User

Advanced

Item

Description

Default

Range

X

X

TARGET

Pool target temperature

85°F

OFF, 55 to 105°F

X

X

DIFF

Differential setting for return sensor

4°F

1 to 20°F

X

BOIL IN MIN

Minimum inlet water temperature

130°F

130 to 150°F

X

BOIL MAX

Maximum outlet temperature

200°F

120 to 200°F

X(*)

SUP TARGET

Supply water temperature

100°F

OFF, 70 to 110°F

X(*)

SUP DIFF

Differential setting for supply sensor

20°F

2 to 20°F

X

MOTOR SPEED

Setting other than 20 may void warranty

20 sec

15 to 30 sec

X

DLY

Time at which purging stops

20 sec

ON, 0:20 to 9:55 min

X

BOIL ON

*Accumulated runtime of unit

0 hr

0 to 999 hr

X

X

F/C Units

Set temperature at °F or °C

°F

°C or °F

User Settings: Rear dip switch set to “1” position.
Advanced Settings: Rear dip switch set to “0” position.
(*) If equipped with optional pool supply sensor.

Adjust Menu Settings for Operating Modes

Appendix B

View Menu Item

Menu Description

Current Temperature

Pool return sensor temperature

TARGET Set point

Pool temperature set point

BOIL IN

Inlet sensor temperature

BOIL OUT

Outlet sensor temperature

BOIL

ΔT

Heater differential temperature

SUP (If equipped pool supply sensor)

Pool supply sensor temperature

BOIL ON (Advanced switch set to “0”)

Accumulated runtime hours

View Menu Information

Installation and Service Manual