13. Remove the manometer and related fitting from the “inlet”

side of the gas valve, replace 1/8" hex plug in the gas valve
and tighten.

14. Turn on the gas supply at the manual valve, turn on L.P.

gas at the tank if required.

15. Turn the power switch to the “ON” position.

16. Turn the gas valve knobs to the “ON” position.

17. Set the temperature control to call for heat.

ƽ

WARNING: After completing any testing on

the gas system, leak test all gas connections.
Apply a soap/water solution to all gas
connections while main burners are operating.
Bubbles forming indicate a leak. Repair all leaks
at once. Do not operate this pool heater with a
leak in the gas train, valves or related piping.

Check burner performance by cycling the system while you
observe burner response. Burners should ignite promptly.
Flame pattern should be stable, see Burner Flames, page 47.
Turn system off and allow burners to cool, then cycle burners
again to ensure proper ignition and flame characteristics.

Figure 30 – Measuring Gas Supply Pressure at
Combination Gas Valve

Installation and Service Manual

29

Nominal Iron

Length of Pipe In Straight Feet

Pipe Size,
(Inches)

10

20

30

40

50

60

70

80

90

100

125

150

175

200

3/4

"

369

256

205

174

155

141

128

121

113

106

95

86

79

74

1"

697

477

384

328

292

267

246

256

210

200

179

164

149

138

1 1/4

"

1,400

974

789

677

595

543

502

472

441

410

369

333

308

287

1 1/2

"

2,150

1,500

1,210

1,020

923

830

769

707

666

636

564

513

472

441

2"

4,100

2,820

2,260

1,950

1,720

1,560

1,440

1,330

1,250

1,180

1,100

974

871

820

2-1/2"

6,460

4,460

3,610

3,100

2,720

2,460

2,310

2,100

2,000

1,900

1,700

1,540 1,400

1,300

3"

11,200

7,900

6,400

5,400

4,870

4,410

4,000

3,800

3,540

3,300

3,000

2,720 2,500

2,340

4"

23,500

16,100

13,100

11,100

10,000

9,000

8,300

7,690

7,380

6,870

6,150

5,640 5,130

4,720

TABLE - K

Multiple Unit Installations Gas Supply Pipe Sizing

Maximum capacity of pipe in thousands of BTU’s per hour for gas pressures of 14 Inches Water Column (0.5 PSIG) or less and a total system
pressure drop of 0.5 Inch Water Column (Based on NAT GAS, 1025 BTU’s per Cubic Foot of Gas and 0.60 Specific Gravity).