Remote Mounting of Sensor

You must mount the outside air temperature sensor outside the
building. To mount remote sensors, follow the guidelines
below. Take care to correctly wire sensors to the unit. Erratic
temperature readings can be caused by poor wiring practices.
Twist the wires between the unit and the remote sensor. Turn
wires at least three or four turns per linear foot of wiring. This
provides common mode rejection of some types of electrical
interferences.

1. Do not route temperature sensor wiring with building

power wiring.

2. Do not locate temperature sensor wiring next to control

contactors.

3. Do not locate temperature sensor wiring near electric

motors.

4. Do not locate temperature sensor wiring near welding

equipment.

5. Make sure good mechanical connections are made to the

sensor, any interconnecting wiring and the controller.

6. Do not mount sensor with leadwire end pointing up in an

area where condensation can occur.

7. Use shielded wiring to connect the sensor to the control

when the possibility of an electrically noisy environment
exists. Shielded cable is recommended on all cable runs of
more than 25 feet in length.

Note: Ground the cable shield at the connection to the boiler
temperature control only. Do not ground the shielded cable at
the sensor end.

To maintain temperature accuracy, sensor wires should be at
least 18 AWG, see Table N below.

HOT SURFACE IGNITION SYSTEM

Hot Surface Igniter and Ignition
Control Module

This unit has one ignition module and one hot surface igniter.

Figure 38 - Hot Surface Igniter

Figure 39 - Hot Surface Ignition Control Module

Installation and

Service Manual

33

Wire

Maximum

Gauge

Allowable Length

12 GA

100 ft

14 GA

75 ft

16 GA

50 ft

18 GA

30 ft

TABLE - N

Remote Wire Connection

ƽ Caution: The igniter is extremely fragile, be very
careful when removing. A faulty or damaged hot surface
igniter MUST BE replaced with a Lochinvar PLT3400
igniter. Do not use general purpose field replacement
igniters.