OPERATION

Continued

Figure 34 - Locating Temperature Control

Temperature Control Settings

There are three setting knobs on the temperature control unless
your unit is specified as a boiler only with an outdoor air reset
option. If your unit is a boiler only with an outdoor air reset
option, there are additional controls for this option. They are
explained under Outdoor Air Reset Option, page 31.

The three setting knobs on the temperature control are for Set
Point, Differential, and High-Fire Offset (see Figure 35).

Maximum Set Point Determination

The maximum set point for the control is factory set. Boilers
are set to 230°F max., water heaters are set to 190°F max., and
specialty state and local codes to 200°F.

These maximum set points are established by not
cutting/cutting the OJ1 and OJ2 jumpers located on the right
side of the temperature controller (see Figure 35). The
maximum set point is determined as shown in TABLE-M.

Figure 35 - Temperature Control Setting Knobs

TABLE-L

Maximum

Setpoint

n

Note: Anytime that OJ1 is the only jumper cut, a new
overlay is required under the Set Point knob on the
temperature controller because the scale has changed to a
maximum of 190°F.

Anytime the OJ2 jumper is cut (with or without OJ1), a
new overlay is required under the Set Point knob on the
temperature controller because the scale has changed to a
maximum of 200°F.

Set Point

The Set Point knob specifies the target water temperature in
degrees, Fahrenheit. After the water temperature reaches the
set point, the temperature control shuts off the burners.

Differential

The Differential specifies the number of degrees below the set
point that the control will allow the water temperature to drop
before it brings the unit back on again.

Hydronic Heating Boilers and
Domestic Water Heaters

30

Max.

OJ1

OJ2

Set Point

Connected

Connected

230°F

Cut

Connected

190°F

Connected

Cut

200°F

Cut

Cut

160°F

TABLE - M

Maximum Set Point Determination