Determine boiler location – Lochinvar KNIGHT WH 55 - 399 User Manual
Page 8
1/4" MINIMUM CLEARANCE
AROUND HOT WATER PIPES
1" MINIMUM CLEARANCE
AROUND VENT PIPE
OPEN FRONT
LEFT
0" MINIMUM
RIGHT
0" MINIMUM
FRONT
6" MINIMUM
BOTTOM
0" MINIMUM
TOP
6" MINIMUM
RECOMMENDED SERVICE CLEARANCES:
FRONT: 24”
BOTTOM: 24”
LEFT SIDE: 12”
Figure 1-2 Alcove Installation - Minimum Required Clearances
1/4" MINIMUM CLEARANCE
AROUND HOT WATER PIPES
1" MINIMUM CLEARANCE
AROUND VENT PIPE
CLOSED DOOR
6"
6"
VENTILATING
AIR OPENING
*
*
AREA OF EACH OPENING:
1 SQ. INCH PER 1000 BTU PER HOUR INPUT
WITH A MINIMUM OF 100 SQ. INCHES.
VENTILATING
AIR OPENING
*
TOP
6" MINIMUM
LEFT
0" MINIMUM
BOTTOM
0" MINIMUM
RIGHT
0" MINIMUM
FRONT
6" MINIMUM
RECOMMENDED SERVICE CLEARANCES:
FRONT: 24”
BOTTOM: 24”
LEFT SIDE: 12”
Figure 1-1 Closet Installation - Minimum Required Clearances
ƽ WARNING
For closet installations, CPVC or
stainless steel vent material MUST
BE used in a closet structure due to
elevated temperatures. Failure to
follow this warning could result in
fire, personal injury, or death.
Note: Service clearances are recommendations only.
Note: Service clearances are recommendations only.
ƽ WARNING For alcove installations, CPVC or
stainless steel vent material MUST
BE used in an alcove structure due
to elevated temperatures. Failure
to follow this warning could result
in fire, personal injury, or death.
8
1
Determine boiler location
Installation & Operation Manual