beautypg.com

General, Venting, Install vent and combustion air piping – Lochinvar KNIGHT WH 55 - 399 User Manual

Page 16: Requirements for installation in canada

background image

16

Installation & Operation Manual

3

General

venting

PVC/CPVC Vent piping materials

Use only the materials listed in Table 3A for
vent pipe, and fittings. Failure to comply
could result in severe personal injury, death,
or substantial property damage.

Installation must comply with local
requirements and with the National Fuel
Gas Code, ANSI Z223.1 for U.S. installations
or CSA B149.1 for Canadian installations.

Install vent and combustion air piping

ƽ DANGER

The Knight wall mount boiler must be
vented and supplied with combustion and
ventilation air as described in this section.
Ensure the vent and air piping and the
combustion air supply comply with these
instructions regarding vent system, air
system, and combustion air quality. See also
Section 1 of this manual.

Inspect finished vent and air piping
thoroughly to ensure all are airtight and
comply with the instructions provided and
with all requirements of applicable codes.

Failure to provide a properly installed vent
and air system will cause severe personal
injury or death.

All PVC vent pipes must be glued, properly
supported, and the exhaust must be pitched
a minimum of a 1/4 inch per foot back to
the boiler (to allow drainage of condensate).

ƽ WARNING

NOTICE

ƽ WARNING

ƽ WARNING

For closet and alcove installations, CPVC or
stainless steel material MUST BE used in a
closet/alcove structure. Failure to follow this
warning could result in fire, personal injury,
or death.

NOTICE

Requirements for installation in

Canada

1. Installations must be made with a vent pipe system

certified to ULC-S636.

IPEX is an approved vent manufacturer in Canada

supplying vent material listed to ULC-S636.

2. The first three (3) feet of plastic vent pipe from the

appliance flue outlet must be readily accessible for visual

inspection.

3. The components of the certified vent system must not be

interchanged with other vent systems or unlisted

pipe/fittings.

4. The 2" and 3" Concentric Vent Kits available from

Lochinvar (see Section 4 – Sidewall Termination – Optional

Concentric

Vent) and the 2" and 3" Concentric Vent Kits

available from IPEX are approved for use on the Knight

wall mount boiler. Both kits are listed to the ULC-S636

standard for use in Canada.

For Models 55, 85, and 110 using 2" venting
and Model 285 using 3" venting, the first
seven (7) equivalent feet of vent must be
CPVC (field supplied). This includes any
transition piece used to increase or decrease
the vent diameter. See examples below.

ƽ WARNING

Examples: 1. Seven (7) feet vertical

2. Connector + 90° elbow + 2 feet horizontal

3. One (1) foot vertical + 90° elbow + 1 foot

horizontal

This appliance requires a special venting
system. For stainless steel venting use
an adapter from Table 3B (page 19)
that corresponds with the intended vent
manufacturer to be used. The field provided
vent fittings must be cemented to the CPVC
pipe section using an “All Purpose Cement”
suitable for PVC and CPVC pipe. Use
only the vent materials, primer, and cement
specified in this manual to make the vent
connections. Failure to follow this warning
could result in fire, personal injury, or
death.

Installing vent and air piping

Improper installation of PVC or CPVC
systems may result in injury or death.

ƽ CAUTION

Use only cleaners, primers, and solvents that
are approved for the materials which are
joined together.

NOTICE

1. Work from the boiler to vent or air termination. Do not

exceed the lengths given in this manual for the air or vent

piping.

2. Cut pipe to the required lengths and deburr the inside and

outside of the pipe ends.

3. Chamfer outside of each pipe end to ensure even cement

distribution when joining.

4. Clean all pipe ends and fittings using a clean dry rag.

(Moisture will retard curing and dirt or grease will prevent

adhesion.)

ƽ WARNING Insulation should not be used on PVC

or CPVC venting materials. The use of
insulation will cause increased vent wall
temperatures, which could result in vent
pipe failure.