General, Venting, Protech heat fab z flex – Lochinvar KNIGHT WH 55 - 399 User Manual

Page 19

background image

3

General

venting

(continued)

VENT

3" S.S. INTERMEDIATE
(FOR SAF-T VENT ONLY)

REPLACE APPLIANCE
SECURED CPVC ADAPTER
WITH APPROPRIATE
STAINLESS STEEL ADAPTER
FROM TABLE 3B

Figure 3-10 Near Boiler Stainless Steel Venting
Models 55 - 399

Stainless steel air intake/vent

connections

1. Combustion Air Intake Connector (FIG. 3-10) -

Used to provide combustion air directly to the unit

from outdoors. A fitting is provided on the unit for final

connection. Combustion air piping must be supported

per guidelines listed in the National Mechanical Code,

Section 305, Table 305.4 or as local codes dictate.

2. Vent Connector (FIG. 3-10) - Used to

provide a passageway for conveying combustion gases to

the outside. A transition fitting is provided on the unit for

final connection. Vent piping must be supported per

the National Building Code, Section 305, Table 305.4 or

as local codes dictate.

Maximum allowable combustion air and

vent piping lengths are as follows:

Model

2" Max Vent/

Air

3" Max Vent/

Air

4" Max Vent/

Air

55

*80 feet

100 feet

N/A

85

*50 feet

100 feet

N/A

110

*40 feet

100 feet

N/A

155

N/A

100 feet

N/A

199

N/A

100 feet

N/A

285

N/A

*50 feet

100 feet

399

N/A

N/A

100 feet

Increasing or decreasing the size of the
combustion air or vent piping beyond the
sizes listed in Table 3C is not authorized.

NOTICE

When determining equivalent combustion air and vent length,
add 5 feet for each 90° elbow, 3 feet for each 45° elbow, and 3
feet for the concentric vent kit, see example below.

EXAMPLE: 20 feet of PVC pipe + (4) 90° elbows + (2) 45°
elbows + (1) concentric vent kit = 49 equivalent feet of piping.

Table 3C Maximum Combustion Air and Vent Piping
Lengths

Note: The minimum combustion air and vent piping length is
12 equivalent feet.

The Knight wall mount boiler uses model specific combustion
air intake and vent piping sizes as detailed in Table 3C.

19

Installation & Operation Manual

Table 3B Approved Stainless Steel Terminations and Adapters

Model

ProTech

Heat Fab

Z Flex

FasNSeal

Saf-T Vent

Z-Vent

Boiler

Adapter

Flue

Termination

Intake

Air

Termination

Boiler

Adapter

Intermediate

Adapter

Flue

Termination

Intake

Air

Termination

Boiler

Adapter

Flue

Termination

Intake Air

Termination

55 - 85

303005

FSBS3

FSRC3(R.C)

303889

WH0002

9353BUREZ-1*

9392

5300CI

9314TERM

2SVAKA02 2SVSTP03

2SVSRCX03

2SVSTEX0390

110 -285

303006

WH1003

2SVAKA03

399

303007

FSBS4

FSRC4(R.C)

FSAIH04

303888

WH3004 9454BUREZ-1*

9492

5400CI

9414TERM 2SVAKA04

2SVSTP04

2SVSRCX04

2SVSTEX0490

* = This adapter must be used in addition to the boiler adapter for Saf-T vent pipe as shown in FIG. 3-10, unless approved vent
other than standard diameter is used. Consult a Heat Fab representative for questions.

For Models 55, 85, and 110 using 2" venting
and Model 285 using 3" venting, the first
seven (7) equivalent feet of vent must
be CPVC (field supplied). This includes
any transition piece used to increase or
decrease the vent diameter.

*

ƽ WARNING