36

6

Hydronic piping

-0.50

0.00

0.50

1.00

1.50

2.00

2.50

3.00

0

2

4

6

8

10

12

14

FT

/H

D

FLOW

55
85

0.00

1.00

2.00

3.00

4.00

5.00

6.00

7.00

8.00

9.00

0

2

4

6

8

10

12

14

16

18

20

FT

/H

D

FLOW

110
155

0.00

0.20

0.40

0.60

0.80

1.00

1.20

1.40

1.60

1.80

2.00

0

5

10

15

20

25

30

35

40

45

FT

/H

D

FLOW

399

MODEL

MODEL

MODEL

199
285

MODEL

0.00

0.50

1.00

1.50

2.00

2.50

3.00

3.50

0

5

10

15

20

25

30

35

FLOW

FT

/H

D

Figure 6-2 Pressure Drop vs. Flow

20°F Temperature Rise Applications

Model

GPM

FT/HD

Minimum Pipe

Size

Pump

Grundfos

TACO

B & G

Armstrong

55

5

0.27

1"

UPS 15-58FC (1)

007

NRF-22

E7

85

8

0.94

1"

UPS 15-58FC (1)

007

NRF-22

E7

110

10

1.53

1"

UPS 15-58FC (2)

007

NRF-22

E7

155

15

4.26

1"

UPS 15-58FC (3)

007

NRF-22

E7

199

19

1.13

1.25"

UPS26-99F

0011

NRF-36 (1)

E7

285

27

2.42

1.25"

UPS26-99F

0011

NRF-36 (3)

E7

399

38

1.42

1.5"

UPS26-99F

0012

PL-55

E11

Table 6A Circulator Recommendations for Temperature Rise Applications_20°, 25°, and 35°

25°F Temperature Rise Applications

Model

GPM

FT/HD

Minimum Pipe

Size

Pump

Grundfos

TACO

B & G

Armstrong

55

4

0.17

1"

UPS 15-58FC (1)

007

NRF-22

E7

85

7

0.72

1"

UPS 15-58FC (1)

007

NRF-22

E7

110

8

0.98

1"

UPS 15-58FC (2)

007

NRF-22

E7

155

12

3.13

1"

UPS 15-58FC (3)

007

NRF-36 (1)

E7

199

15

0.71

1.25"

UPS26-99F

0011

NRF-36 (1)

E7

285

22

1.61

1.25"

UPS26-99F

0011

NRF-36 (3)

E7

399

31

0.95

1.5"

UPS26-99F

0012

PL-55

E11

35°F Temperature Rise Applications

Model

GPM

FT/HD

Minimum Pipe

Size

Pump

Grundfos

TACO

B & G

Armstrong

55

3

0.10

1"

UPS 15-58FC (1)

007

NRF-22

E7

85

5

0.37

1"

UPS 15-58FC (1)

007

NRF-22

E7

110

6

0.55

1"

UPS 15-58FC (2)

007

NRF-22

E7

155

9

1.76

1"

UPS 15-58FC (3)

007

NRF-36 (1)

E7

199

11

0.38

1.25"

UPS 15-58FC (3)

0010

NRF-36 (1)

E7

285

16

0.85

1.25"

UPS 15-58FC (3)

0010

NRF-36 (1)

E7

399

22

0.48

1.5"

UPS26-99F

0011

NRF-36 (1)

E7

Pumps listed in bold type are provided by the factory as the boiler circulation pump.

NOTICE

The temperature rise provided by a pump/model combination will decrease by 3% per 1000 feet of elevation.

NOTICE