Chapter 8 mk programming – LG G4F-AD3A User Manual
Page 74
Chapter 8 MK Programming
8 - 8
4) Programming
MOVP 00001 D0000
RPUT hC002 h0001 D0000 00000 00004 M000
Buffer
memory
Start address
of data
No. of
words
Channel to be used
(use channel 0)
Assign analog input
range (0 ~ 10 VDC)
Assign average
processing channel
(channel 0)
Set Averaging count of
channel 0 (10 times)
Send the setting data to
the remote A/D module
via Fnet module at slot 2
P0000
END
MOVP 00001 D0001
MOVP 00001 D0002
MOVP 00010 D0003
Link status
Remote code
of A/D module
Slot number
of A/D module
MOVP 00001 D0011
Validate the setting of
A/D module
RPUT hC002 h0001 D0011 00011 00001 M001
P0000
Send the setting data to
the remote A/D module
via Fnet module at slot 2
RGET hC002 h0001 D0012 00012 00001 M002
F0093
P0000
Read buffer 12 of remote
A/D module per 1
second, and store it to
D0012 of self -station
Buffer
memory
Start address
of data
No. of
words
Link status
Remote code
of A/D module
Slot number
of A/D module
Slot number of
Fnet module
Station number of
Fnet remote module
P0010
< 2000 D0012
P0000
Turns on P0010 when
the digital value is less
than 2000
P0011
< D0012 3000
>= D0012 2000
Turns on P0011 when
the digital value is 2000
~ 2999
P0012
< D0012 4000
>= D0012 3000
Turns on P0012 when
the digital value is 3000
~ 3999
P0013
>= D0012 4000
Turns on P0013 when
the digital value is 4000
or greater
Slot number of
Fnet module
Station number of
Fnet remote module