beautypg.com

4 i/o conversion characteristics, Remark – LG G4F-AD3A User Manual

Page 18

background image

Chapter 2. SPECIFICATIONS


2 - 7

Input / Output (hereafter I/O) conversion characteristics are expressed with the angle of the line between

analog input(voltage and current) and matched digital value.
I/O conversion characteristics of the G3F-AD3A, G4F-AD3A are expressed with Fig 2.1, and I/O conversion

characteristics of the G6F-AD2A is expressed with Fig 2.2

The voltage or current input for a channel is selected by analog input selection switch and the value of
Offset / Gain can not be changed because it is fixed.


















[Fig 2.1] I/O Conversion Characteristics



REMARK

1. The analog output value of over 4047 or –48 is fixed as 4047 or –48.

2. Keep the input voltage and current not to exceed +15V and 25mA.


2.4 I/O Conversion Characteristics

Practical analog input range

Digital

Output

Value

4000

3000

2000

1000

0

0V

5V

10V

1V

3V

5V

4

12

20

DC 0 ~ 10V

DC 1 ~ 5V

DC 4 ~ 20

Analog

Input

-0.12V

3.808

0.952V

10.12V

20.192

5.048V

4047

-48

This manual is related to the following products: