beautypg.com

Caution – LG G4F-AD3A User Manual

Page 14

background image

Chapter 2. SPECIFICATIONS


2 - 3

2) G6F-AD2A

Items

Specifications

I/O points

16 points

Voltage

1 ~ 5 VDC (input resistance 1 )

0 ~ 10 VDC (input resistance 1 )
-10 ~ 10VDC (input resistance 1 )

Current

DC4 ~ 20 mA (input resistance 250 )

Analog

input

Voltage/Current selection

- Selection with Terminal
( It has to be connected between V and I terminal to select current. )
- Selection of voltage range by switch on the side of module

Digital output

-

12 bit binary value(-48 ~ 4047, -2048 ~ 2047)

-

Digital output value is selected by program.

1 ~ 5VDC

1 mV (1/4000)

0 ~ 10VDC

2.5 mV (1/4000)

-10 ~10VDC

5 mV (1/4000)

Maximum

resolution

DC 4 ~20mA

4 (1/4000)

Overall Accuracy

0.5% (accuracy to full scale)

Max . conversion speed

5.0 ms/channel

Max . absolute input

Voltage : 15V, Current : 25mA

Number of analog input point

4 channels/module

Isolation

Between input terminals and PLC: Photo coupler isolation

(Between channels : Non-isolated)

Terminals connected

18-point terminal block

+5VDC

40mA

+15VDC

50mA

Current

Consumption

-15VDC

20mA

Weight

200g

[Table 2.2] Performance Specifications

CAUTION

The factory-set value of A/D conversion module has been current input mode.
The G6F-AD2A has to be used with the GM6-PAFB.

!