Chapter 4. FUNCTION BLOCK

4 - 9

2) G6F-AD2A

Function block for reading the module is performed for every channel in block and the specified channels
are used to read output variable of data displayed from A/D conversion digital value.

Function

block

I/O

Variable

Data

type

Descriptions

REQ

BOOL

Function Block Execution Request Area

- The execution of read function block is requested in this area.

- If the status to be connected with this area is satisfied on the program operation

and input condition changes from low(0) to high(1), function block reading for the

module is executed.

NET_

NO

USINT

The location number of the slot on which the communication module of the master

station is mounted.

- Setting range: 0 to 7

ST_NO

USINT

The station number of the communication module which a remote I/O station has.

- Setting range : 0 to 63

BASE

USINT

Base Module Location Number Area

- The base No. on which A/D conversion module is mounted is written on this area.

- Setting range : 0

SLOT

USINT

Slot Location Number Area

- The slot No. on which A/D conversion module is mounted is written on this area.

- Setting range: 0 to 7

Input

CH

BOOL[4]

Available Channel Specification Area

- Available channels are specified in this area.

- Enabled channels are specified to 1 and disabled channels are specified to 0.

NDR

BOOL

When function block execution is completed with no error, 1 is written. During the scan

which the execution condition has been made, 1 is continuing and at the next scan. 0

is written.

ERR

BOOL

Error Data Display Area

- When error occurs during the execution of function block reading, 1 is written and

the operation come s to stop. During the scan which the execution condition has

been made, 1 is continuing and at the next scan, 0 is written.

STAT

USINT

Error Code Display Area

- When error occurs during the execution of function block reading, the error code

number is written.

ACT

BOOL[4]

Channel Operation Display Area
- The channel specified after executing the function block reading with no error is

right, 1 is written and, on the non-specified channel, 0 is written.

Output

DATA

INT[4]

A/D Conversion Value Output Area

- Data output range : -48 ~ 4047


REMARK

BOOL[4] and USINT[4] of data type means that the number of element is 4, and also this means the whole number of channels and channel number.

ST_N
O

BASE

SLOT

CH

ADR62RD

DATA

STAT

REQ

NET_
NO

ERR

NDR