LG G4F-AD3A User Manual
Page 73

Chapter 8 MK Programming
8 - 7
8.2.3 An A/D module mounted on a remote station
1) System configuration
Fnet communication module on self-station : slot 2
Fnet remote module of remote station : station number 01
A/D module of remote station : slot 0, remote code = hC0
2) Initial setting of A/D module
No
Item
Setting
Buffer memory
address
Data to be
written
1
Channel to be used
Ch 0
0
h0001
2
Analog input type and range
0 ~ 10 VDC
1
h0001
3
Averaging processing enable
Ch 0
2
h0001
4
Averaging count
Ch 0 : 10 times
3
h000A
5
Validate setting
7
h0001
3) Description of program
When the digital converted value of channel 0 of remote A/D module is less than
2000, turns on P0010 of self-station.
When the digital converted value of channel 0 of remote A/D module is 2000 ~ 2999,
turns on P0011 of self-station.
When the digital converted value of channel 0 of remote A/D module is 3000 ~ 3999,
turns on P0012 of self-station.
When the digital converted value of channel 0 of remote A/D module is 4000 or
greater, turns on P0013 of self-station.
GM4-
PA2A
K4P-
15AS
G4X-
D22A
G4Q-
TR2A
G4L-
FUEA
P000
P001
P002
GM4-
PA2A
G4L-
RBEA
G4F-
AD3A
G4Q-
TR2A
Station
number : 01
Slot 0
P0000
Start switch for A/D
conversion