Table 32 mechanical characteristics, Table 33 rectifier ac input (mains), Table 32 – Liebert Emerson NX UPS System User Manual
Page 82: Mechanical characteristics, Table 33, Rectifier ac input (mains)

Technical Specifications
74
Table 32
Mechanical characteristics
Rated Power, kVA
Unit of
Measurement
10
15
20
30
Dimensions, WxDxH
mm (in)
600x700x1400
(23-9/16x27-5/8x55)
Mass
Mass without batteries
kg (lb)
180 (397)
204 (450)
204 (450)
210 (463)
Finish
N/A
Pantone 877 (Silver grey)
equivalent Becker Silver epoxy polyester powder 041-37-2
Protection Degree, IEC (60529)
N/A
IP20 (finger-proof with front doors open or closed)
Table 33
Rectifier AC input (mains)
Rated Power, kVA
Unit of
Measurement
10
15
20
30
Rated AC Input Voltage
VAC
380/400/415
(3-phase and sharing neutral with the bypass input)
Input Voltage Tolerance
2
VAC
305V to 477V
304V to 208V (output derated below 70%)
Frequency
Hz
50/60Hz (tolerance 40Hz to 70Hz)
Power Factor
kW/kVA, full
load
(half load)
0.99 (0.98)
Input Power
kVA rated
(maximum
8.9 (11.7)
13.3 (18.9)
17.8 (23.3)
26.6 (35.0)
Input Current
A rated
(maximum
12.9 (16.9)
19.3 (27.4)
25.8 (33.8)
38.6 (50.7)
Harmonic Current Distortion
THDI % FL
3
3
3
3
Duration of Progressive
Power Walk-In
sec
10 seconds to reach full rated current
(selectable 5 through 30 seconds in 5-second intervals)
1. Rectifier operates at any of the rated supply voltages and frequencies without further adjustment.
2. At 305V input mains the UPS maintains the specified output voltage at rated load without discharging a previously charged
battery
3. IEC 62040-3 / EN 50091-3: at rated load and input voltage 400V, battery charged
4. IEC 62040-3 / EN 50091-3: at rated load and input voltage 400V, battery charging at maximum rated power.