3 external circuit-breaker interface, Table 5 external circuit-breaker interface, Figure 4 jumper connection for bcb interface – Liebert Emerson NX UPS System User Manual
Page 21: External circuit-breaker interface, Figure 4, Jumper connection for bcb interface, Table 5
![background image](/manuals/165366/21/background.png)
Single Module UPS Installation
13
1.8.3 External Circuit-Breaker Interface
J10 is the interface to any external battery circuit breaker (BCB).
Figure 4
Jumper connection for BCB interface
Table 5
External circuit-breaker interface
Position
Name
Description
J10.1
DRV
BCB Driver Signal - (reserved)
J10.2
FB
BCB Contact State -(reserved)
J10.3
GND
Power Ground
J10.4
OL
BCB On-Line - Input - This pin will become active when BCB interface is connected. (N.O.)
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm
2
(16-20AWG) stranded for maximum runs between 25 and 50 meters (82-164ft.) respectively.
UPS Monitoring Board
J10
OL
DR
V
GN
D
FB
Battery Circuit Breaker
OL
Aux – N.O.
Aux – N.O.
See also other documents in the category Liebert Tools:
- PS250-50S (12 pages)
- SGH STEAM SL-14050 (16 pages)
- Ship-Ahead Input/Output Cabinet NXL (20 pages)
- NfinityTM (44 pages)
- 4000 (59 pages)
- 230V (40 pages)
- PSP (32 pages)
- UPStation GXT (20 pages)
- UPSTATION GXT 2U (38 pages)
- UPS Systems PSI XR (32 pages)
- 600TTM (91 pages)
- Series 600T (128 pages)
- GXT2 - 3X1 (42 pages)
- Nfinity (44 pages)
- PowerSure PSA 350VA to 1000VA (8 pages)
- 2U (16 pages)
- PDUTM (156 pages)
- GXT2-6000 RT208 (52 pages)
- PowerSure Personal (12 pages)
- 2700VA (40 pages)
- Series 610 (44 pages)
- GXT 2U (44 pages)
- UPStation S VM12000 (38 pages)
- 1000kVA (120 pages)
- Nfinity 208 V / 240 V 60Hz (45 pages)
- UPS (28 pages)
- UPS System (121 pages)
- PowerSure PSI 1000 - 3000VA 60 Hz 120V (36 pages)
- GXT2-4500RT230 (40 pages)
- GXT2-6000RTL630 (44 pages)
- IntelliRack (2 pages)
- PowerSure PSA 350-1000VA (2 pages)
- 350-700 VA (11 pages)
- 500-650 VA (24 pages)
- PowerSure PS250-60S (13 pages)
- 130 kVA (102 pages)
- 30-130kVA (112 pages)
- GXT (23 pages)
- PSITM (34 pages)
- 600T (88 pages)
- 600T (73 pages)
- 610 (104 pages)
- GXTTM (30 pages)
- 700-3000 VA (30 pages)