beautypg.com

4 output dry contacts, Figure 5 output dry contacts and epo wiring, Table 6 output dry contact relays – Liebert Emerson NX UPS System User Manual

Page 22: Output dry contacts, Figure 5, Output dry contacts and epo wiring, Table 6, Output dry contact relays

background image

Single Module UPS Installation

14

1.8.4 Output Dry Contacts

There are three output dry contact relays at the X1 slot (see Figure 5 and Table 6)

Figure 5

Output dry contacts and EPO wiring

Table 6

Output dry contact relays

Position

Name

Description

J13.2

BFP_O

Bypass feedback protection relay; normally open; closed when bypass SCR is shorted

J13.3

BFP_S

Bypass feedback protection relay center

J13.4

BFP_C

Bypass feedback protection relay; normally closed; open when bypass SCR is shorted

J21.2

INV_O

Inverter mode relay; normally open; closed when UPS is in inverter mode

J21.3

INV_S

Inverter mode relay center

J21.4

INV_C

Inverter mode relay; normally closed. Opened when UPS is in inverter mode

J25.2

ACF_O

Main input fault relay; normally open. Closed when main input is in fault

J25.3

ACF_S

Main input fault relay center

J25.4

ACF_C

Main input fault relay; normally closed. Open when main input is in fault

NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm

2

(16-20AWG) stranded for maximum runs between 25 and 50 meters (82-164ft.) respectively.

EPO - NC

EPO - NO

X2

X1

BFP_C

J21

J25

J28

BFP_

S

BF

P_

O

INV_O

INV_

S

INV_

C

AC

F

_

C

ACF_

S

AC

F_O

J13

+12V