4 output dry contacts, Figure 5 output dry contacts and epo wiring, Table 6 output dry contact relays – Liebert Emerson NX UPS System User Manual
Page 22: Output dry contacts, Figure 5, Output dry contacts and epo wiring, Table 6, Output dry contact relays
Single Module UPS Installation
14
1.8.4 Output Dry Contacts
There are three output dry contact relays at the X1 slot (see Figure 5 and Table 6)
Figure 5
Output dry contacts and EPO wiring
Table 6
Output dry contact relays
Position
Name
Description
J13.2
BFP_O
Bypass feedback protection relay; normally open; closed when bypass SCR is shorted
J13.3
BFP_S
Bypass feedback protection relay center
J13.4
BFP_C
Bypass feedback protection relay; normally closed; open when bypass SCR is shorted
J21.2
INV_O
Inverter mode relay; normally open; closed when UPS is in inverter mode
J21.3
INV_S
Inverter mode relay center
J21.4
INV_C
Inverter mode relay; normally closed. Opened when UPS is in inverter mode
J25.2
ACF_O
Main input fault relay; normally open. Closed when main input is in fault
J25.3
ACF_S
Main input fault relay center
J25.4
ACF_C
Main input fault relay; normally closed. Open when main input is in fault
NOTE
All auxiliary cables of terminal must be double-insulated. Wire should be 0.5-1.5mm
2
(16-20AWG) stranded for maximum runs between 25 and 50 meters (82-164ft.) respectively.
EPO - NC
EPO - NO
X2
X1
BFP_C
J21
J25
J28
BFP_
S
BF
P_
O
INV_O
INV_
S
INV_
C
AC
F
_
C
ACF_
S
AC
F_O
J13
+12V