STRIP 1/2"

FROM WIRE

TO BE ATTACHED.

1/2" (13MM)

TWIST WIRES

TOGETHER WITH

PLIERS (MINIMUM

OF THREE TURNS)

INSERT TWISTED WIRES

UNDER TERMINAL AND

TIGHTEN. CHECK FOR

A GOOD MECHANICAL

CONNECTION.

FIG. 60 Wire Termination for E-Bus Connection

1.

Strip 1/2 in. (13 mm) in su la tion from the conductor.

2.

Insert the wire in the required terminal location
and tighten the screw to complete the termination.

3.

If two or more wires are being inserted into one
terminal location, twist the wires together a
minimum of three turns before inserting them.

4.

Cut the twisted end of the wires to 3/16 in. (5 mm)
before inserting them into the terminal and
tightening the screw.

5.

Pull on each wire in all terminals to check for
good mechanical connection.

Wire Requirements

The minimum type and grade of wire required to “net work” the
Intelli-Fin to other units or LonMark

®

devices is a Level IV,

22 AWG (0.034 mm

2

) plenum or non-plenum rated (as applicable),

unshielded, twisted pair, stranded com

mu

ni

ca

tion wire. The

following man u fac tur ers supply com mu ni ca tion wire that meets or
exceeds this specification for E-Bus connections.

Anixter

(847) 677-2600
www.anixter.com

__________________________________________________

Belden Wire and Cable Co.

(800) 235-3361
www.belden.com

__________________________________________________

BICC General

(800) 424-5666
www.biccgeneral.com

(BICC Cable, Brand-Rex, General Cable, Carol Cable)

__________________________________________________

ConnectAir International

(800) 247-1978
www.connect-air.com

__________________________________________________

Eastman Wire & Cable

(800) 257-7940
www.eastmanwire.com

__________________________________________________

Honeywell Inc.

(800) 345-6770
www.honeywell.com

__________________________________________________

Lucent Technologies

(305) 569-3600
www.lucent.com/netsys/

systimax

__________________________________________________

Windy City Wire

(800) 379-1191
www.smartwire.com

__________________________________________________

NOTE:

The minimum specification for Level IV, 22 AWG
(0.034 mm

2

) unshielded, twisted pair, stranded

communication cable must be plenum-rated when the wire
is routed through air ducts or plenum areas. Non-plenum
rated communication cable is for general use when the wire
is not being routed through air ducts or plenum areas.

ADDITIONAL COMPONENTS

USED TO INTERFACE

MULTIPLE APPLIANCES

Serial LonTalk® Adapter (SLTA) — A serial LonTalk

®

adapter is

required to provide communication between the
E-Bus and either a PC serial port or an approved modem using the
SLTA-10 EIA-232 port. The SLTA interfaces with LonSpec

TM

software. There are specific null modem cable requirements for
proper connection to a modem. The SLTA has a DB-9 female
connection. Direct connection to a PC can be made with a DB-9 to
DB-9 cable or a DB-9 to DB-25 cable, based on the available PC
connection.

FTT Repeater — A repeater is available to increase the network
wiring length in an E-Bus network. The repeater is designed to be
installed in a standard field supplied 4 by 4 junction box.

Excel 15 — The Excel 15 Building Manager is a LonMark

®

compliant device that provides network management functions for
the E-Bus in a Light Commercial Building Solutions System. The
Excel 15 is compatible with the E-Bus and uses the free topology
transceiver (FTT). Individual Excel 15 Controllers and
Communicating Subbases distributed on the E-Bus perform
specific HVAC equipment control. The Excel 15 monitors and
controls both local and remote controller points. If E-Bus
communications are interrupted, the Excel 15 is capable of
stand-alone operation.