CHIMNEY

3' MIN

2' MIN

10' OR LESS

CHIMNEY

2' MIN

WALL OR
PARAPET

FIG. 15

Vent Termination from Flat Roof - 10 Feet or
Less from Parapet Wall

3' MIN

10' OR MORE

CHIMNEY

WALL OR

PARAPET

NOTE: NO HEIGHT

ABOVE PARAPET

REQUIRED WHEN

DISTANCE FOR

WALLS OR PARAPETS

IS MORE THAN 10'>

FIG. 16

Vent Termination from Flat Roof - 10 Feet or
More from Parapet Wall

A vertical termination less than 10 feet (3.05 m) from a parapet
wall must be a minimum of 2 feet (0.61 m) higher than the
parapet wall.

SIDEWALL VENTING

TERMINATIONS

This venting system uses the ap pli ance’s internal combustion air
blower to force the flue products out of a horizontally-terminated
flue. This blower generates a positive pres sure in the flue.
Combustion air is drawn from the equipment room (see
Combustion and Ventilation Air Re

quire

ments) unless the

appliance is equipped with an optional Direct Vent or Intelli-Vent
System.

FIG. 17 Sidewall Venting Installation

The connection from the appliance flue outlet to the sidewall vent
cap MUST be made with listed type Category IV vent materials
and accessories. The in

stall

er must supply suitable vent pipe

material. The sidewall vent cap is available from the appliance
manufacturer as a vent kit.

FIG. 18 Sidewall Vent Cap

TABLE - E

Sidewall Vent Cap Kits

Sidewall Vent

Input Btu/hr Flue Size Cap Kit

1,500,000

________________

1,700,000

________________

2,000,000

6"

_____________

7"

_____________

8"

SVK3026

_________________

SVK3027

_________________

SVK3028

The sidewall vent cap kit includes the wall penetration assembly
and the dis charge screen assembly. All required Category IV vent
pipe and fittings must be purchased locally.