Checking equipment do not warning ƽ, What to do if you smell gas, Owner warning ƽ – Lochinvar 000 through 2 User Manual
Page 3: Important, Codes warning ƽ, Warning ƽ
Upon receiving equipment, check for signs of ship ping damage.
Pay par tic u lar attention to parts ac com pa ny ing the boiler, which
may show signs of being hit or otherwise being mishandled. Verify
total number of pieces shown on packing slip with those actually
re ceived. In case there is damage or a shortage, immedi ate ly notify
carrier.
CHECKING EQUIPMENT
DO NOT
WARNING
ƽ
Do not use this appliance if any part has been under water.
The possible damage to a flooded appliance can be extensive
and present numerous safety hazards. Any appliance that
has been under water must be replaced.
If the information in this manual is not followed exactly, a
fire or explosion may result causing property damage,
personal injury or loss of life.
This appliance MUST NOT be installed in any location
where gasoline or flammable vapors are likely to be present,
unless the installation is such to eliminate the probable
ignition of gasoline or flammable vapors.
WHAT TO DO IF YOU SMELL GAS
•
Do not try to light any appliance.
•
Do not touch any electric switch: do not use any phone in
your building.
•
Immediately call your gas supplier from a neighbor’s
phone. Follow the gas supplier’s instructions.
•
If you cannot reach your gas supplier, call the fire
department.
Installation and service must be performed by a
qualified installer, service agency or the gas
supplier.
OWNER WARNING
ƽ
The information contained in this manual is intended
for use by qualified professional installers, service
technicians or gas suppliers. Consult your local expert
for proper installation or service procedures.
IMPORTANT
Consult and follow local Building and Fire Regulations and
other Safety Codes that apply to this installation. Contact
the local gas utility company to authorize and inspect all gas
and flue connections.
A gas appliance that draws combustion air from the equipment
room where it is installed must have a supply of fresh air circulating
around it during burner operation for proper gas combustion and
proper venting.
1. Boilers and water heaters are heat producing appliances.
To avoid damage or injury, do not store materials against
the appliance or the vent-air intake system. Use proper care
to avoid unnecessary contact (especially children) with the
appliance and vent-air intake components.
2. Never cover your appliance, lean anything against it, store
trash or debris near it, stand on it or in any way block the
flow of fresh air to your appliance.
3.
UNDER NO CIRCUMSTANCES must flammable
materials such as gasoline or paint thinner be used or stored
in the vicinity of this appliance, vent-air intake system or
any location from which fumes could reach the appliance
or vent-air intake system.
The equipment shall be installed in accordance with those
installation regulations in force in the local area where the
installation is to be made. These shall be carefully followed in all
cases. Authorities having ju ris dic tion shall be consulted before
instal la tions are made. In the absence of such requirements, the
installation shall conform to the latest edition of the National Fuel
Gas Code, ANSI Z223.1 and/or CAN/CGA-B149 Installation Code.
Where required by the author i ty having jurisdiction, the in stal la tion
must conform to American Society of Mechanical Engineers Safety
Code for Controls and Safety Devices for Au to mat i cal ly Fired
Boilers, ASME CSD-1. All boilers conform to the latest edi tion of
the ASME Boiler and Pressure Vessel Code, Section IV. Where
required by the authority having ju ris dic tion, the installation must
comply with the CSA International, CAN/CGA-B149 and/or local
codes. This appliance meets the safe lighting performance criteria
with the gas man i fold and control assembly provided, as specified
in the ANSI standards for gas-fired units, ANSI Z21.13.
CODES
WARNING
ƽ
Should overheating occur or the gas supply fail to shut off,
DO NOT
turn off or disconnect the electrical supply to
the pump. Instead, shut off the gas supply at a location
external to the appliance.
WARNING
ƽ
To minimize the possibility of serious personal injury, fire or
damage to your appliance, never violate the following safety
rules.
3