Troubleshooting guide (continued) – Kenmore Power Miser 9 Gas Water Heater 153.33096 User Manual
Page 29
29
PROBLEM
POSSIBLE CAUSE(S)
CORRECTIVE ACTION
DRIP FROM RELIEF VALVE
1. Excessive water pressure
2. Closed water system
1. Use a pressure reducing valve and relief
valve
2. See “Thermal Expansion”
THERMOSTAT FAILS TO
SHUT OFF
1. Non-functioning
thermostat
2. Improper
calibration
1. Replace
thermostat
2. Replace
thermostat
COMBUSTION ODORS
1. Insufficient air
2. Water heater flue or vent system blocked.
3. Heater installed in a confined area
1. Provide ventilation to water heater.
Check flue
way, flue baffle, and burner
2. Clean, locate source and correct
3. Provide fresh air ventilation
SMOKING AND CARBON
FORMATION (SOOTING)
1. Flammable vapor incident
1. Call 1-800-4-MY-HOME
®
(1-800-469-4663)
CONDENSATION
1. Temperature setting too low
1. Increase the temperature setting
BURNER FLAME FLOATS
AND LIFTS OFF PORTS
1. Orifice too large
2. High gas pressure
3. Water heater flue or vent system blocked.
4. Cold
drafts
5. Dirty burner screen
1. Replace with correct orifice
2. Check with gas utility company
3. Clean flue and burner-locate source and
correct
4. Locate source and correct
5. Clean burner screen. See “Ultra Low
NOx Natural Gas Burner” section of this
manual.
FLAME BURNS AT ORIFICE
1. Non-functioning
thermostat
2. Low gas pressure
3. Non-functioning
burner
1. Replace
thermostat
2. Check with gas utility company
3. Replace burner assembly
PILOT FLAME TOO SMALL
1. Pilot line or orifice clogged
2. Low gas pressure
3. Dirty
pilot
1. Clean, locate source and correct
2. Check with gas utility company
3. Clean
pilot
TROUBLESHOOTING GUIDE (Continued)